Search faults and breakdowns of split systems McQuay/Acson, it is necessary to start with the common causes of breakdowns and equipment failure. Common causes include electrical malfunctions and malfunctions of the refrigeration circuit.

Name of McQuay/Acson equipment, their analogues and modifications.
McQuay MWM007/10/15/25/GR
MWM009J/JR, AWM009J/JR
M5WM010J/JR, A5WM010J/JR
MWM015J/JR, AWM015J/JR
M5WM015J/JR, A5WM015J/JR
Acson AWM 07/10/10/20/50GR

McQuay diagnostics using the remote control:

  • 1. Press and hold the TIMER CANCEL button for 5 seconds, 00 blinks on the display.
  • 2. Press the TIMER CANCEL button until a long beep appears, which indicates the error code,
    present in the code table and shown on the display.
  • 3. A short beep or two consecutive beeps displays inappropriate error codes.
  • 4. To cancel the display of the error code on the display, press and hold the TIMER CANCEL button for
    within 5 seconds. If this button is not pressed within 1 minute, it will automatically
    canceling the display of the code on the display.

controller, - McQuay and Acson error code

E1 McQuay/Acson low gas pressure faults, see air conditioner outdoor unit

Name of split systems, air conditioners.

E2 High gas pressure fault, see air conditioner outdoor unit
E3 Compressor overload, check the mains voltage, if necessary, set the current characteristics according to the rating, read the data on the panel.
E4 Malfunction of the temperature sensor McQuay
E5 Compressor liquid hit, poor evaporation in the indoor unit of the Acson split system
F2 Closed, temperature sensor does not work, malfunction
F4 Air temperature sensor does not work, check the resistance
F6 Check the connections, are we confusing the wires? It's like blondes confuse pedals.))
F9 No compression refrigerant leak agent, burst nut, poor flaring,
FE no compression refrigerant leak agent
h3 Current protection tripped, check compressor temperature sensor
H4 McQuay/Acson High Pressure Sensor Malfunctions
L1 Low pressure compression
L3 The temperature sensor of the outdoor unit has tripped, frostbite, - when working on heat.
L4 Water flow switch defective
L5 sensor is faulty, check the resistance of the sensor, 10-16 ohms

The code McQuay errors- Causes

troubleshooting

If one of the main development problems, refer to the following information for a description of possible causes and corrective steps:

Neither the fan nor the compressor is running (no power)

  • 1. The fuse may be blown or the switch is open. Checking electrical circuits and motor windings for shorts or bases.
    Investigate for possible overloads.
    Replace the fuse or reset switches after the problem is corrected.
  • 2. Wires can be loose or break. Tighten or replace. Throw away the split.
  • 3. The supply voltage may be too low. Check it out with the power company.
  • 4. The control system may be faulty. Check thermostat for proper connection and check 24 volt transformer for burnout.

Fan runs but compressor does not run

    1. Check compressor condenser.

2. Wires can be loose or break. Tighten or replace.
3. The high pressure switch may have tripped due to:
a) a contaminated or connected capacitor;
b) no or no condenser water;
c) Too warm condenser water;
d) Not enough airflow over the coils due to dirty filters.
5. Check thermostat, calibration and wiring.
6. Compressor overload protection is open. If the compressor thermocouple is overheated, the overloads will not be reset
until it gets cold. If the overload is external, replace it. If the overload is internal, winding shorted, replace the compressor.
7. Compressor winding may be defective. Check continuity with an ohmmeter. If the windings are broken, replace the compressor.

Compressor - attempts to start, but the compressor stops

1. Check the integrity of the McQuay contactor relay.
2. McQuay. Check system pressure, high?
3. High superheat leads to freezing.
4. Lack of refrigerant.

Compressor stops after running for a short time

    1. Checking the thermostat.

Air conditioner detail, outdoor unit

McQuay/Acson faults

2. Check system pressure.
3. Refer to troubleshooting - 3 possible causes.

Insufficient cooling or heating

  • 1. Checking the thermostat.
  • 2. The air flow may not be sufficient. Check and clean the filter.
  • 3. The check valve is defective, creating ice in the refrigerant. Check check valve
    valve coil.
  • 4. Insufficient ventilation, freezing of the indoor unit of the system. condensate does not drain. Add ventilation rate.
  • 5. Make sure any block is in the water outlet, or if the water is dirty.
  • 6. Lack of refrigerant.

Insufficient water flow through the condenser (pipe in pipe) drain hose crease

    1. Check the valves are open.
    2. Check for security atmospheric air trapped in pipelines.
    3. Check the circulation pump. Acson

dripping water

1. Check the condensate drain.
2. Check the condition of the filters.
3. Check if the condensate drain runs uphill.
4. See if the motor fan is up to speed.
5. Check fan position.
6. Is the drainpipe properly trap?

Noisy air conditioner outdoor unit

    1. Check the fan impellers, what they are clinging to.
    2. Check for dents in the impeller.
    3. Check if there are free fan wheels on the shaft.
    4. Check if the compressor tubes are touching. Adjust the tubes by bending slightly.
    5. Check all screws on the panels.
    6. Check drain. Remove the ice!!! When working on heat, - freezing of the evaporator.

Features

Excellent Air Distribution

Air discharge direction can be adjusted in four directions, manually or automatically by using LCD remote
control.

The new double louver design with automatic air swing function fully optimizes the room comfort by
distributing the air evenly to the room. The unique skew fan design with larger diameter creates better air flow
to the operating environment.

self diagnosis
    This function is able to detect and to disgnose any faults occurring in the system by blinking of the LED lights.
    Simplify and ease for troubleshooting.
Facilitated Maintenance Ensure

Calculation Steps remote control.

    The new design of air discharge housing where by the fan blower can be easily accessed by just losing
    two screws on the unit to provides a flexible, faster and easier way to clean up the fan blower and ionizer.
    Maintenance is easy for electrical components, piping and wiring as these are all easily accessible by simply
    removing front plastic panel.
High Efficiency Heat Exchanger

The compact design of the 3-fold structure heat exchanger provides a large surface are for better and efficient
heat exchange. The unique Hydrophilic slit fin has greatly improved the air flow and the contact surfaces with
the air thus to boost the cooling capacity.

Wireless remote controller

  • The compact LCD transmitter is able to operate the air conditioner unit within the distance of 9 meters.
  • Fan motor speed can be set at low / medium / high or automatic.
  • Sleep mode auto control will gradually increase or decrease the setting temperature to provide a
    comfortable surroundings for sleeping.
  • Air flow direction can be controlled automatically.
  • Room temperature is controlled by electronic thermostat.
  • The real time timer allows the air conditioner to be switched on and off automatically based on user
    settings.
  • Turbo mode function is available to enables the required set temperature to be achieved in a short time
  • Personalized setting allows user to preset and store 2 groups of personal settings (including timer setting)
    in the handset.

Auto random restart is a function where by when there is power failure occurred during operation, the unit
will automatically restart as the last setting condition once the power is resumed.

  • Page 1 SERVICE GUIDE BOOK...
  • Page 2: Table Of Contents

    © 2012 Mcquay International. All rights reserved throughout the world. Bulletin illustrations cover the general appearance of Mcquay International products at the time of publication. We reserve the right to change design and construction specification at any time without notice...
  • Page 3: Model Name

    MCQUAY Service Guide Book Model Name 1.0 MODEL NAME 1.1 Product Name Description Description Generic Model Name MCQUAY Brand Wall Mounted Fan Coil Unit WM / 5WM MWM / M5WM Wall Mounted AC Inverter Fan Coil Unit MWMV Wall Mounted DC Inverter Fan Coil Unit...
  • Page 4: Conversion Table 2.1 Conversion Table

    MCQUAY Service Guide Book Conversion Table 2.0 CONVERSION TABLE 2.1 Conversion Table Capacity Btu/hr kCal/Hr 0.001 0.252 0.293 x 10 1000 0.293 3.968 0.004 1.162 x 10 3412 3.412 860.04 Pressure W.G. Pascal kg/cm (in.) (ft.) (Pa) 0.07 27.7 2.309 0.69 x 10...
  • Page 5: Product Mainboard Vs Handset Matrix

    MCQUAY Service Guide Book Product Mainboard vs. Handset Matrix 3.0 PRODUCT MAINBOARD VS. HANDSET MATRIX 3.1 Product Mainboard vs. Handset Matrix Main Board 2P2065 Handset R_1_ W_2_ C_2_ Type No. L2.0 VA2.0 VA3.0 Model 69-4 SB125 Standard Optional WM - F Series...
  • Page 6 MCQUAY Service Guide Book Product Mainboard vs. Handset Matrix Type Main Board (IC) Handset MC1.0 LWS2 APM01CB APM02D Standard Optional Model WM – GW Series SLM3+AC5300/Netware 3/SLM8 CK – AW/MWH/CW Series SLM3+AC5300/Netware 3/SLM8 CE – DW Series SLM3+AC5300/Netware 3/SLM8 CW FCU CE –...
  • Page 7: Handset Operating Guide

    MCQUAY Service Guide Book Handset Operating Guide 4.0 HANDSET OPERATING GUIDE 4.1 G6 Operation Guide 1. “ON/OFF” Switch 2. Temperature Setting 5. Timer Setting Press button to activate the timer setting Press button to increase or decrease (from 1 hour to 15 hour) of the air the set temperature.
  • Page 8 MCQUAY Service Guide Book Handset Operating Guide 4.2 G7 Operation Guide 10. Sleep Mode Setting This function is available under COOL, 1. Transmission Source HEAT & AUTO mode. 2. Signal Transmission Indication When it is activated in COOL mode, ...
  • Page 9: G11

    MCQUAY Service Guide Book Handset Operating Guide 4.3 G11 8. Sleep Mode Setting This function is available under COOL, HEAT and AUTO mode. When the unit is operating under cooling mode, the set temperature is increased by 0.5°C after 30 minutes, 1°C after an hour, and 2°C after 2 hours.
  • Page 10: G17

    MCQUAY Service Guide Book Handset Operating Guide 4.4 G17 6a. Silent Function (For WM - J Series only) Press for quiet operation. Fan speed turn to minimum speed. Press again to deactivate the function. 6b. Ionizer Function (For WM - G series only) ...
  • Page 11: Gs01

    MCQUAY Service Guide Book Handset Operating Guide 4.5 GS01 Operation Guide Swing mode selection (for CK-E model) Press SWING button for 4 seconds to 1. Transmission Source enter field setting mode. While in field setting mode, it will only 2.
  • Page 12 MCQUAY Service Guide Book Handset Operating Guide Any change of fan speed will deactivate this function. The Turbo function is unavailable for chilled water system and remote control with SWING MODE function. 8. OFF timer setting 9. Quiet function (model dependant) ...
  • Page 13: Apj1

    MCQUAY Service Guide Book Handset Operating Guide 4.6 APJ1 Operation Guide 1. Transmission Source To cancel POWERFUL operation, press button again. disappears 2. LCD Display from the LCD. 3. ECONO button 5. Temperature settings. ECON operation is a function which enables efficient operation by limiting the 6.
  • Page 14 MCQUAY Service Guide Book Handset Operating Guide The flap (horizontal blade) will begin to To cancel OFF TIMER operation, press swing. button. will disappear from the To set the flap at desired position, press LCD. button when the flap has reached the desired position.
  • Page 15: Slm3

    MCQUAY Service Guide Book Handset Operating Guide 4.7 SLM3 Operation Guide 1. “ON/OFF” Switch after 30 minutes, 1°C after 1 hour and 2°C after 2 hours. If it is activated under 2. Temperature Setting “HEAT” mode operation, temperature will be decreased 0.5°C after Setting range are between 16°C to 30°C...
  • Page 16: Slm8

    MCQUAY Service Guide Book Handset Operating Guide 4.8 SLM8 While in field setting mode, it will only show SWING MODE Press temperature button select SWING MODE rotation from Swing Mode 1 to Swing Mode 3. There are 3 different SWING MODE,...
  • Page 17 MCQUAY Service Guide Book Handset Operating Guide Set Event 1 and Event 2 Timers Press the same key again will increase Process for Timer ON and Timer OFF is the setting to 2 hours. An indicator the same.
  • Page 18: Sequential LCD

    MCQUAY Service Guide Book Handset Operating Guide 4.8 Sequential Controller 5. Temperature Setting To set the desired room temperature, press to increase or decrease the set temperature in the range of 16°C to 30°C. Press both simultaneously to toggle between °C and °F setting.
  • Page 19: Netware 3/3c

    MCQUAY Service Guide Book Handset Operating Guide 1. Time display 2. Key lock display 3. Error indication 4. Fan speed display 5. Operation mode display 6. Sleep mode display 7. Air swing display 8. Temperature set display Jumper Application 20 - 30 Set temp range: 20°C ~ 30°C...
  • Page 20: Rooftop Panel

    MCQUAY Service Guide Book Handset Operating Guide When it is activated in HEAT mode, the This timer can be controlled separately set temperature will be decreased 1°C through remote control as well as ON after 30mins, 2°C after 1 hour and 3°C TIMER or OFF TIMER keys.
  • Page 21 MCQUAY Service Guide Book Handset Operating Guide Operating Guide 1. LCD Display Upon power up of the unit, the LCD 6. ECS Button displays the main display screen 7. Downward Button Press the button once to view the...
  • Page 22: Chiller Panel

    MCQUAY Service Guide Book Handset Operating Guide 4.11 Chiller Panel Operating Guide 1. LCD Display The panel can keep up to 20 faults/alarm warning records. Upon power up of the unit, the LCD displays the main display screen 6.
  • Page 23: Mc301

    MCQUAY Service Guide Book Handset Operating Guide 4.12 MC301 Operating Guide 1. ON/OFF Operation 6. Auxiliary Heater Setting Press “ON/OFF” key, the unit will be ON or OFF, and “ON” or “OFF” will display on Under “HEAT” or “FAN” mode, press the LCD.
  • Page 24 MCQUAY Service Guide Book Handset Operating Guide 10. Reset Exit timer setting: If there is no press on This key is used to reset the unit. any key within 5s or press any key except “▲”, “▼”, “TIMER” and “ON/OFF” key, it 11.
  • Page 25: Mc303

    MCQUAY Service Guide Book Handset Operating Guide 4.13 MC303 Operating Guide 1. Address Register Press the “MODE” button, the current After communication wire is completely mode is twinkling. Press again to change connected, press “SETUP” key for 5s.
  • Page 26 MCQUAY Service Guide Book Handset Operating Guide 10. Indoor unit lock/unlock Enter first timer setting, the timer ON or Press “UNIT No.” key to enter the unit OFF icon will display on the left and bottom of LCD panel, the timer sequence setting, then press “▲”...
  • Page 27: Controller Setting

    MCQUAY Service Guide Book Controller Configuration 5.0 CONTROLLER SETTING 5.1 Auto Random Restart 5.2 Hot Keep Selection Three selections available: Shorted at JH/JP1/J_LST jumper at main a. Fan stop if indoor coil temperature< 30°C board for auto restart (supplied).
  • Page 28 MCQUAY Service Guide Book Controller Configuration L2 Models L208A / LWS2.0 models Two selections are available: There are 2 tables setting for HT_KP & MODEL jumpers as shown as below. a. Fan ON: - If the indoor coil temperature > 40°C, the indoor fan will run at speed.
  • Page 29: Sequential Board (sq2.0)

    MCQUAY Service Guide Book Controller Configuration 5.3 Sequential Board (SQ2.0) Dip switch setting of sequential controller are as the following: Dip switch 3 Dip switch 4 a. default b. 0.5°C c. 1.0°C d. 1.5°C Note: 1.5°C only valid for 2 and 3 compressors model.
  • Page 30 MCQUAY Service Guide Book Controller Configuration 6. Defrost Option Select whether compressor will turn off or remain on when 4WV changes at the beginning of defrost cycle. Dip switch 8 a. Compressor off b. Compressor on On (C2.4 spec) 7. Summary of Models available...
  • Page 31: Chilled Water Fan Coil Unit - W1v3

    MCQUAY Service Guide Book Controller Configuration 5.4 Chilled Water Fan Coil Unit (W1V3) The standard W1V3 board comes with a VALVE jumper. The system can be configured as the jumper selection listed below: Model: MCK 20-50AW, MCK 15-25BW, MCK 10-...
  • Page 32: Chilled Water Fan Coil Unit - W2.0

    Valve less √ : Jumper Remained X: Jumper Removed VALVE & HEAT Jumper Location Model: MWM - G2W / 301W Heat 1. VALVE jumper is plugged into JVLV Jumper connector on the emergency switchboard.
  • Page 33: Hardware Setting - Slm8

    MCQUAY Service Guide Book Controller Configuration 5.6 Hardware Setting – SLM8 There are 2 jumpers on SLM8 option to control the board function as shown in Picture below. 20-30C TURBO_ QUIET Summary of Hardware Setting as table below: Jumper Short...
  • Page 34: Conversion Configuration

    MCQUAY Service Guide Book Controller Configuration 6.0 CONVERSION CONFIGURATION 6.1 Auxiliary Heater Conversion U1.5 Heatpump with Auxiliary Heater To convert the standard U1.5 heatpump PCB to 1. Heater relay (240V/20A) auxiliary heater application, following 2. Transistor, 2SC945 components need to be added onto the PCB: 3.
  • 1. Place the JM Relay (240V/20A) on the heater application, only need to add one heater RY_HTR location relay as shown below: 2 .
  • 1. Shunt jumper heater application, the following components 2. JM Relay 240VAC/ 20A need to be added onto the PCB: Step 1:- Place the shunt jumper at jumper header M2.
  • Page 37: Multi-Split Conversion

    Controller Configuration 6.2 Multi Split Conversion Cooling Only Model (L2.0 / L208A) Heatpump Models (L208A) MWM-G, MCK-A/B/C/E, MCM-E, MCC-C which MCK-AR/BR/CR /ER, MCM-ER, MCC-CR are using L2 control board can be switched to multi split units without any modification needed. The multisplit can be selected by using shunt jumper and short jumper header MODEL_KP between pin 1 &...
  • Page 38: U1.5 L208a Conversion

    MCQUAY Service Guide Book Controller Configuration 6.3 U1.5 L208A Conversion All single split indoor units with U1.5 PCB cannot 1. L2 08A Heat Pump PCB. be directly replaced by the new L208A PCB 2. Room sensor, indoor coil sensor inter-...
  • Page 39: Wmf U1.4 To L2ef Conversion

    MCQUAY Service Guide Book Controller Configuration 6.4 WMF U1.4 to L2EF Conversion 1. The U1.4 PCB can be replaced directly by the 3. only the display panel or On/Off switch board new L2EF PCB because no modification from U1.4 to L2EF or L2EF to U1.4.
  • Page 40: Sq Board For Wiring Up To 1000m Conversion

    MCQUAY Service Guide Book Controller Configuration 6.5 SQ Board for Wiring up to 1000m Conversion Comparison of Sequential Main Board SQMB01 Before & After conversion: Before IC:MAX1483 J1 removed J2 removed After Work Indication (WI): PART: 2051-MAX1483 IC:MAX1483 Step 1: Remove Jumper J1 and J2.
  • Page 41 MCQUAY Service Guide Book Controller Configuration Sequential LCD conversion for wiring up to 1000m Work Indication (WI): Step 1: Dismantle the BACK cover of Sequential LCD. Step 2: Remove Jumper J1, J2. Step 3: Add Chip Resistor 1/10W 5% 200K to R8, R9 and R10.
  • Page 42: Room Sensor On Netware

    MCQUAY Service Guide Book Controller Configuration 6.6 Room Sensor on Netware 3 There is a temperature sensor located at TH1 on the Netware 3 controller board as shown in the picture below. The temperature sensor is optional and can be used as room sensor, so that room...
  • Page 43: Service Diagnosis

    MCQUAY Service Guide Book Diagnosis 7.0 SERVICE DIAGNOSIS 7.1 LED Lights Diagnosis Table Wall Mounted F Series Cooling Only Model Board Handset MWM 10/15/20/25F, 311 D2.0 MWM 07/10/15/20/25F L2EF POWER SLEEP TIMER Operation / Faulty Action Indication (Green) (Red) (Orange)
  • Page 44 MCQUAY Service Guide Book Diagnosis Wall Mounted F Series Heat Pump Model Board Handset MWM 10/15/20/25FR, 301R U1.5 G7 / SLM3 / Netware 3 / SLM8 MWM 07/10/15/20/25FR, 311/ 301R L2EF COLD HEAT SLEEP Error Code Operation / (SLM3 / Faulty...
  • Page 45 MCQUAY Service Guide Book Diagnosis Wall Mounted G Series Model Board Handset MWM 10/15/20/25G/GR L2.2 G17 / SLM3 / Netware 3 / SLM8 SLEEP POWER TIMER IONIZER Error Operation / Faulty Code Action Indication (SLM3 / ( Red) (Orange) (Green) Netware 3)
  • Page 46 MCQUAY Service Guide Book Diagnosis Wall Mounted J Series Model Board Handset MWM 09/15J/JR L2GSN SLEEP POWER TIMER Error Operation / Faulty Action Code Indication (Red) (Green/Red) (Orange) Cooling mode Green Heating mode Auto mode in heating operation Auto mode in cooling...
  • Page 47 MCQUAY Service Guide Book Diagnosis Ceiling Cassette A / B / C Series Model Model Board Handset MCK 20/25/30/40/50A/AR U1.5 G7 / SLM3 / Netware 3 / SLM8 MCK 15/20/25B/BR U1.5 G7 / SLM3 / Netware 3 / SLM8 MCK 10/15/20C/CR U1.5...
  • Page 48 MCQUAY Service Guide Book Diagnosis Ceiling Cassette A / B / C/ E Series Model Model Board Handset MCK 20/25/30/40/50A/AR L208A G17 / SLM3 / Netware 3 / SLM8 MCK 15/20/25B/BR L208A G17 / SLM3 / Netware 3 / SLM8...
  • Page 49 MCQUAY Service Guide Book Diagnosis Ceiling Exposed D Series Model Model Board Handset MCM 20/25/30/40/50D/DR U1.5 G7 / SLM3 / Netware 3 / SLM8 COOL HEAT Error Code Operation / Faulty (SLM3 / Action Indication Netware 3) (Green) (Orange) (Green)
  • Page 50 MCQUAY Service Guide Book Diagnosis Ceiling Exposed D / E Series Model Model Board Handset MCM 20/25/30/40/50D/DR L208A G17 / SLM3 / Netware 3 / SLM8 MCM 15/20/25/28E/ER L208A G17 / SLM3 / Netware 3 / SLM8 COOL HEAT Error Code...
  • Page 51 MCQUAY Service Guide Book Diagnosis Chilled Water Fan Coil Unit Model Board Handset MWM 05 – 25FW, 301W W1V3 G7 / SLM3 / Netware 3 / SLM8 MCK 20 – 50AW/MWH W1V3 G7 / SLM3 / Netware 3 / SLM8 MCK 15 –.. .
  • Page 52 MCQUAY Service Guide Book Diagnosis Water Source Split Unit – Wall Mounted G Series Model Model Board Handset M5WMWS 10/15/20/25GR LWS2.0 G17 / SLM3 / Netware 3 / SLM8 SLEEP POWER TIMER IONIZER Error Code Operation / Faulty (SLM3 /...
  • Page 53 MCQUAY Service Guide Book Diagnosis Water Source Split Unit – Ceiling Cassette A / B / C Series Model Model Board Handset M5CKWS 20/25/30/40/50AR LWS2.0 G17 / SLM3 / Netware 3 / SLM8 M5CKWS 10/15/ 20CR LWS2.0 G17/SLM3/Netware 3/SLM8...
  • Page 54 MCQUAY Service Guide Book Diagnosis Wall Mounted F Cooling Only Inverter-X Model Model Board Handset MWMX 10/15F VA2.0 G17 / SLM3 TIMER SLEEP POWER Error Operation / Faulty Code Action Indication (SLM3) (Orange) (Red) (Green ) (Orange) Timer On Sleep mode On...
  • Page 55 MCQUAY Service Guide Book Diagnosis Wall Mounted F Heatpump Inverter-X Model Model Board Handset MWMX 10/15FR VA2.0 G17 / SLM3 STAND- Error COOL/DRY HEAT BY/FAN TIMER Operation / Faulty Code Action Indication (SLM3) (Green ) (Red) (Orange) (Orange) Cooling mode Dry mode...
  • Page 56 MCQUAY Service Guide Book Diagnosis Wall Mounted G Series Inverter-X Model Model Board Handset MWMX 10/15/20/25G/GR VA2.0 G17 / SLM3 SLEEP POWER TIMER IONIZER Error Operation / Faulty Code Action Indication (SLM3) (Red ) (Orange) (Green) (Green/Red) Cooling mode Heating mode / Standby...
  • Page 57 MCQUAY Service Guide Book Diagnosis Ceiling Cassette A/C Series Inverter-X Model Model Board Handset MCKX 20/25A/AR VA3.0 G17 / SLM3 MCKX 10/15/20C/CR VA3.0 G17 / SLM3 POWER TIMER SLEEP HEAT Error Operation / Faulty Code Action Indication (SLM3) (Green) (Orange)
  • Page 58 MCQUAY Service Guide Book Diagnosis Ceiling Convertible E Series Inverter-X Model Model Board Handset MCMX 15/20/25E/ER VA3.0 G17 / SLM3 COOL HEAT Error Operation / Faulty Code Action Indication (SLM3) (Green) (Orange) (Green) (Red) Cooling mode Dry mode Fan mode...
  • Page 59 MCQUAY Service Guide Book Diagnosis Inverter - X Outdoor Unit Model Board MLCX 10/15/20/25C/CR VB2.0 MMSV 25/35A VB2.0 AMSX 20/25/30A/AR VB2.0 Normal running / compressor running RED LED blinking No. of Blinks Blinking Indication Normal running, with no limitation Voltage limit...
  • Page 60 MCQUAY Service Guide Book Diagnosis Inverter-Y Model Indoor Series Model Board Handset M5WMY 10/15/20/25 JR W_2_03A GS01 / G17 M5CKY 10/15/20CR C_2_01A GS01 / G17 / Netware 3C M5CKY 20/25/28/40 /50 ER C_2_01A GS01 / G17 / Netware 3C A5CMY 62 CR...
  • Page 61 MCQUAY Service Guide Book Diagnosis Single Split Inverter – Y Outdoor Unit Model Board M5LCY 10/15 DR S_2_03A M5LCY 20/25 CR S_2_04A M5LCY 30/40/50/60 FR Error code diagnosis by Outdoor 7-segment Display In the Y- series model, the 7-segment display section on the outdoor unit indicates the following: 1.
  • Page 62 MCQUAY Service Guide Book Diagnosis Multi Split Inverter – Y Outdoor Unit Model Board M5MSY 20/25/30 BR The unit outdoor LED indicates the running condition of the system: LED INDICATION Green Description NORMAL ● ● ● ● INSTALLATION ERROR ANTIFREEZE (OTHER ROOMS ) HEAT SINK OVERHEAT ●...
  • Page 63: Error Codes Diagnosis By Handset

    MCQUAY Service Guide Book Diagnosis 7.2 Error Codes Diagnosis By Handset SLM 3 / Netware 3 / SLM 9 – On/Off Models Error Code Faulty Indication Room air sensor contact loose / short Indoor coil sensor contact open Outdoor coil sensor contact open...
  • Error Error Faulty Indication Faulty Indication Code Code Normal Outdoor air thermistor short/open Indoor PCB error Pressure sensor error Compressor discharge pipe thermistor Drain pump fault...
  • Page 65 MCQUAY Service Guide Book Diagnosis Sequential Controller (SQ LCD) – SB & RT Multi Compressors Error Error Faulty Indication Faulty Indication Code Code Require manual reset (possible causes) Indoor coil sensor 4 short Compressor 1 high temperature (overload) Indoor coil sensor 1 open...
  • Page 66 MCQUAY Service Guide Book Diagnosis Rooftop Panel Alarm Shown On The Rooftop Panel Whenever panel received a new alarm, an alarm message will pop up on the LCD. It shows type of alarm, alarm occurred time and date. Backlight blinking (if Backlight is not OFF) and alarms buzzer produces beeping sound (if it's set ON).
  • Page 67 MCQUAY Service Guide Book Diagnosis Condenser fan motor faulty Replace fan motor. Main PCB faulty Replace main PCB. 9. Disconnection of Poor sensor connection Connect correctly and operate again. discharge thermistor 1 / 2 10. Heat Exchanger 1 / 2...
  • Page 68 MCQUAY Service Guide Book Diagnosis Chiller Panel – Air Cooled Mini Chiller When malfunctioning occurred, the display LCD will blink. The display will show the faulty parameter and the date and time of the occurrence. When a malfunction of the unit is detected, immediately switch off the main power supply before...
  • Page 69 MCQUAY Service Guide Book Diagnosis G17 – Inverter Y Models Temperature Display Section MODE Button TIMER CANCEL Button OFF TIMER Button Diagnosis Step 1. Hold down TIMER CANCEL button for 5 seconds, a “ ” indication flashes on the temperature display section.
  • Page 70 MCQUAY Service Guide Book Diagnosis GS01 – Inverter Y Models Diagnosis Step 1. Hold down ON TIMER CANCEL button or OFF TIMER CANCEL button for 5 seconds, a “ ” indication flashes on the temperature display section. 2. Press TIMER CANCEL repeatedly until indoor buzzer produces a long beep. This indicates the error code, refers to Error Codes table and is displayed on the temperature display section.
  • Page 71 MCQUAY Service Guide Book Diagnosis Error Codes for G17 and GS01 – Inverter Y Models Error Error Error Description Error Description Codes Codes Normal Discharge pipe overheat Insufficient gas Heat exchanger overheat DC voltage out of range Compressor sensor system abnormality...
  • Page 72 MCQUAY Service Guide Book Diagnosis APJ1 –M5WMY10/15KR Indoor LED Indication Timer Cancel The operation lamp (green) flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation.
  • Page 73: Mds Diagnosis

    MCQUAY Service Guide Book Diagnosis 7.3 MDS Diagnosis (A)Indoor Units Model Board Handset A(5)WMD 09/10/15/20/25 G MC201-C A(5)CKD 20/25/30/40/50 A MC201 -C A(5)CKD 10/15/20 C MC201-C A(5)CMD 20/25/28 E MC201-C A(5)CMD 40/50 D MC201-C A(5)CMD 62 C MC201 -C A(5)CCD 10/15/20/25/30/40/50/60 C...
  • Page 74 MCQUAY Service Guide Book Diagnosis Error Diagnosis by Wired Controller (MC301) ITEM CODE DESCRIPTION Sensor Broken (indoor outlet coil) Sensor Broken (indoor return air) Sensor Broken (indoor supply air) Indoor and controller communication malfunction Ambient temp exceed the limit 4WV malfunction...
  • Page 75 MCQUAY Service Guide Book Diagnosis (B) Outdoor Units Model Board Handset MDS 30/40/50/60/70 A/AR V4.0 – V4.5 G17/ MC301 MDS 80/100/120/150/180/200 /240/ V2.0 – V2.7 G17/ MC301 260/300/320 V/BR 5MDS 80/100/120/140/160/180/ 200/220/240/260/280/300/320/340/ 360 V2.1A – V2.6A G17/ MC301 /380/400/420/440/460/480/500 B/BR Error code diagnosis by PCB four Digit 7-Segment...
  • Page 76: General Check

    MCQUAY Service Guide Book Diagnosis 7.4 General Check When any air conditioner malfunction is noted, immediately switch off the power supply to the unit and contact the local dealer if necessary. Problem Symptom Check Item Suggested Action The unit does not...
  • Page 77: General Troubleshooting Guide

    MCQUAY Service Guide Book Diagnosis 7.5 General Troubleshooting Guide By means of pressure readings: Pressure Probable Cause Data Circuit 1. Overcharged with refrigerant. High Side 2. Non-condensable gases in refrigerant Low Side circuit (eg. Oil) 3. Obstructed air-intake / discharge.
  • Page 78: Appendix

    MCQUAY Service Guide Book Appendix APPENDIX A. Resistance – Temperature Characteristics Model ALL ON/OFF UNIT, FAN COIL UNIT Resistance R25=10.0kΩ + 1.0% - 1.0% B Value B25/30=3450K + 1.0% - 1.0% T°C Rmin (kΩ) Rnom (kΩ) Rmax (kΩ) T°C Rmin (kΩ) Rnom (kΩ)
  • Page 79 MCQUAY Service Guide Book Appendix Model M5WMY10/15KR; M5LCY10/15ER; M5LCY30/40/50/60FR Resistance R25=20.0kΩ + 1.0% - 1.0% T°C A (kΩ) B (kΩ) T°C A (kΩ) B (kΩ) T°C A (kΩ) B (kΩ) 197.81 192.08 25.01 24.45 4.96 4.87 189.53 181.16 23.91 23.37 4.79...
  • Page 80 MCQUAY Service Guide Book Appendix Model M5LCY30/40/50/60FR Discharge Pipe Sensor Resistance R25=230.0kΩ + 1.0% - 1.0% Resistance Resistance Resistance Resistance T°C T°C T°C T°C (kΩ) (kΩ) (kΩ ) (kΩ) 1120.0 109.0 18.1 1002.5 100.2 16.9 898.6 92.2 15.8 806.5 84.9 14.8 724.8...
  • Page 81: Mds Compatibility

    MCQUAY Service Guide Book Appendix B. MDS Compatibility Indoor PCB vs Wired Handset MC301 MC301 B1.5 B1.6 B.17 B1.8 B1.9 B2.0 B2.1 Indoor mc201_2.0 mc201_2.1 mc201_2.2 mc201_2.3 mc201_2.4 mc201_2.5 mc201_2.6 mc201_2.7 Indoor PCB vs Outdoor PCB MDS-A/B 7HP and Below:...
  • Page 82: Mds Outdoor Capacity Dip Switch Setting

    MCQUAY Service Guide Book Appendix C. MDS Outdoor Capacity Dip Switch Setting MDS-B PCB version 2.3 and below: Dip Switch S3.1 S3.2 S3.3 S3.4 10HP 12HP 15HP 18HP 20HP 22HP 26HP 28HP 32HP MDS-B PCB version 2.4 and above: Dip Switch S2.3...
  • Page 83: Cable Length Of Wired Handset

    MCQUAY Service Guide Book Appendix D. Cable Length of Wired Handset Cable Length (m) Wired Handset Cable Type Standard Optional Maximum UL2547 SLM 3 2.2m, 7m 10m, 15m AWG26 UL2547 Netware 3 AWG26 UL2547 Netware 3C AWG26 UL2547 SQ-LCD Not Provided. ..
  • Page 84 ©2012 McQuay International www.mcquayup.com...

This section contains all instructions for McQuay equipment (USA) in Russian, English language. Documents can be downloaded in pdf format or opened directly on the site.

    • Controllers AC 512, 513, 2800 A/B, 8000. Operation manual. Language: RU | pdf 247.79 Kb

      Fan coil controllers W1V3, W2 (electronic board). Reference guide. Language: RU | pdf 1.58 Mb

      Smart Manager Controller. Centralized control of chillers and fan coils. Instruction manual. pdf 885.98 Kb

      G4 wireless remote control for MDS systems. Manual. Language: RU | pdf 150.95 Kb

      G6 - wireless remote control. Manual. Language: RU | pdf 213.27 Kb

      MCCCS02B(MC303) is a wired centralized controller for MDS systems. Manual. Language: RU | pdf 238.82 Kb

      Control panels AC 8000C for fan coils MFU, MCW. User's manual. Language: EN | pdf 400.65 Kb

    • Characteristics of 2-way and 3-way valves used with McQuay fan coils. Installation instructions. Language: RU | pdf 1.65 Mb

    • MLC 07 series outdoor units B. Spare parts list. Language: RU | pdf 696.58 Kb

      MWM 007-010E,ER. Wall type air conditioners. Spare parts list. Language: RU | pdf 1.22 Mb

      Indoor units MHSB 030-060 A/ AR. Spare parts list. Language: RU | pdf 255.50 Kb

      External blocks of the MMC 030-060 AB series. Spare parts list. Language: RU | pdf 1.52 Mb

      MMSD 1010/1015/1515 series outdoor units A. Spare parts list. Language: RU | pdf 642.25 Kb

      Channel fancoils of the MCC series. Reference Guide 2009 2009 | Language: RU | pdf 5.30 Mb

      Cassette split systems of the CC-SL series. Instructions for installation and operation. Language: EN | pdf 316.04 Kb

      Cassette split systems of the CK-SL series. Instructions for installation and operation. Language: EN | pdf 272.21 Kb

      MWSD 010/015/020 ER/FR/CR, MMSD, MMST. Multi-split systems of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.33 Mb

      M5MSX 020/025/030AR. Wall-mounted multi-split systems with inverter direct current. Technical guide. Language: RU | pdf 3.75 Mb

      M5MSY 20/25/30BR. Multi-split systems. Technical guide. Language: RU | pdf 3.41 Mb

      Ceiling split systems models MCM020D/DR, MCM025D/DR, MCM030D/DR, MCM040D/DR, MCM050D/DR Complete service manual. Language: EN | pdf 2.03 Mb

      MCK-A. Ceiling cassette conditioners of separate type of series A (ceiling). Installation guide. Language: RU | pdf 375.75 Kb

      MCK 020/025/030/040/050AR. Split air conditioners cassette type. Installation, operation and maintenance manual. Language: RU | pdf 824.71 Kb

      MCK-S. Ceiling cassette conditioners of separate type of series C (ceiling). Installation guide. Language: RU | pdf 501.84 Kb

      MSK 020-050A, AR. Cassette type air conditioners. Spare parts list. Language: RU | pdf 512.03 Kb

      MWM 015/020/025 F, C, CR, FR. Split-air conditioners of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.96 Mb

      MWM 007-025 G/GR. Split-air conditioners of wall type. Technical guide. Language: RU | pdf 3.75 Mb

      MWM 007/010 E/ER. Split-air conditioners of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.50 Mb

      Split air conditioners wall series G. List of changes and additions to the reference manual. Language: RU | pdf 920.69 Kb

      CC 10/15/20/25 CW, CC 30/40/50/60 CW. Split-ceiling two-chamber air conditioners, with water-cooled fan. Installation guide. Language: RU, EN | pdf 596.12 Kb

      MCM 020/025/030/040/050DR. Split air conditioners of universal (floor-ceiling) type. Manual for installation, operation and maintenance. Language: RU | pdf 934.66 Kb

      MCM 020-025D. Floor-to-ceiling type air conditioners. Spare parts list. Language: RU | pdf 1.02 Mb

      MFU. Features of installation of fan-coils of the MFU series. Installation instructions. Language: RU, EN | pdf 316.46 Kb

      CK 20/25/30/40/50 AWH/ Series A fan coils for 4-pipe systems. Installation instructions. Language: RU, EN | pdf 523.89 Kb

      MCW 200 C/H/F - MCW 1200 CHW. Frameless subceiling fan coils. Instructions for installation and operation. Language: RU, EN | pdf 720.78 Kb

      MCW 200 CD - MCW 1200 CD. Ceiling fan coils. Instructions for installation, operation and installation. Language: RU, EN | pdf 1.14 Mb

      SB 75/100/125/150 BW, MDB 075/100/125/150 BW. Fan-coils of the SB series. Installation guide. Language: RU, EN | pdf 1.20 Mb

      WM 05/07/10/15/20/25 FW, MWM 005/007/010/015/020/025 FW. Fan-coils with water cooling for wall installation. Installation guide. Language: RU, EN | pdf 816.15 Kb

      Fan-coils MWM 010-025 FW. Specification. Language: RU, EN | pdf 47.65 Kb

      Fan-coils of the CB and D series (ceiling-mounted). Installation instructions. Language: RU, EN | pdf 3.07 Mb

      Fan-coils of the G series (wall-mounted). Installation instructions. Language: RU, EN | pdf 2.91 Mb

    • MWP 05A~06A series water-cooled air conditioners. Instructions for installation, operation and maintenance. Language: EN | pdf 1.51 Mb

      AWS units. Air-cooled chillers with screw compressors. Instructions for installation and operation. Language: RU | pdf 1.24 Mb

      McEnergy MONO units. Air cooled chiller with single screw compressor. Installation, operation and maintenance manual. Language: RU | pdf 1.99 Mb

      Air-cooled mini chillers of the AMAC 080-150C/CR-A4AC80-150C/CR series. Instructions for installation and operation. Language: RU | pdf 3.04 Mb

      Air-cooled mini chillers of the AMAC 080C/CR-A4AC150C/CR series. Instructions for installation and operation. Language: RU | pdf 1.90 Mb

      Air-cooled mini chillers M4AC040-058AE/ARE, 075-125BE/BRE series. Instructions for installation and operation. Language: EN | pdf 962.72 Kb

      Air-cooled mini chillers MAC040-058A/AR, MAC075-125B/BR series. Instructions for installation and operation. Language: RU | pdf 1.52 Mb

      Air-cooled mini chillers MAC/M4AC080-150 C/CR series. Instructions for installation and operation. Language: EN | pdf 1.05 Mb

      Mini-chillers of the MAC-040, MAC-050, MAC-058 series. Instructions for installation and operation. Language: RU | pdf 706.15 Kb

      Mini-chillers of MAC-075 B/BR, MAC-100 B/BR, MAC-125 B/BR series. Instructions for installation and operation. Language: RU | pdf 666.29 Kb

      Multizone systems MDS. Design and installation guide. Language: RU, EN | pdf 3.58 Mb

      Multizone systems MDS. Installation guide. Language: RU, EN | pdf 3.36 Mb

      5RT 90/120/150/180BR. Rooftops. Installation guide. Language: RU, EN | pdf 2.68 Mb

      MRT 080/100/150/180A/AR. Roof top air conditioners. Instructions for installation, operation and maintenance. Language: RU, EN | pdf 1.48 Mb

      MRT/M4RT. Stand-alone rooftop air conditioners. Technical guide. Language: RU, EN | pdf 3.17 Mb

      MDB 075/100/125DR. High-pressure split-air conditioners of channel type. Technical guide. Instructions for installation, operation and maintenance. Language: RU | pdf 1.79 Mb

      MCC 010-025C,CR. Channel type air conditioners. Spare parts list. Language: RU | pdf 123.26 Kb

      MCC 015/020/025/030/040BR. Channel type air conditioners. Installation, operation and maintenance manual. Language: RU | pdf 1.07 Mb

      MDB 040-100B,BR. Channel type air conditioners. Spare parts list. Language: RU | pdf 910.46 Kb

      MDB 200-750 B, 075-500 D, 075-100 BR, 125 CR, 150-500 BR. Channel split systems. Technical guide. Language: RU | pdf 8.23 ​​Mb

      MHSB 030-060AR. Channel type air conditioners. Installation, operation and maintenance manual. Language: RU | pdf 746.88 Kb

      Separate type static fan air conditioners (Rooftops) of the SB, MSB, HSB series - (cooling only); SL, MSS (external). Installation and operating instructions. Language: RU | pdf 371.12 Kb

      Fan coil units of the MCC-010BW-040BW, MCM-020DW-050DW, MCK-020AW-050DW series. Instructions for installation and operation. Language: RU | pdf 2.11 Mb

      Fancoils of the MMSB, MHSB, MDB series. Instructions for installation and operation. Language: EN | pdf 1.97 Mb

      Language: EN | pdf 707.19 Kb

      Fan-coils vertical series MFU-C/H, MFC-C/H. Instructions for installation and operation. Language: RU | pdf 522.15 Kb

      Fan-coils built-in ceiling series MCC/ACC10-60CW. Instructions for installation and operation. Language: RU | pdf 1.61 Mb

      Fan-coils channel ADB/MDB075-150BW series. Instructions for installation and operation. Language: RU | pdf 1006.41 Kb

      Fan-coils channel series MCW200-1200C/H. Instructions for installation and operation. Language: RU | pdf 1.95 Mb

      Fan-coils channel series MCW200-1200C/H. Installation and operating instructions (English). Language: RU | pdf 2.60 Mb

      Fan-coils floor-ceiling, channel, cassette series ACK, RCM, RCC 10-50. Instructions for installation and operation. Language: RU | pdf 1.07 Mb

      Language: RU | pdf 187.65 Kb

      Fan-coils wall series MWM10-25FW. Instructions for installation and operation. Language: EN | pdf 186.03 Kb

      Fan-coils of the MCK, MCM, MCC 010-050 BW, DW, AW series. Instructions for installation and operation. Language: RU | pdf 2.84 Mb

      Fan coils of the MWM-FW, MCM-DW, MCK-AW/BW, MDB-BW series. Instructions for installation and operation. Language: EN | pdf 5.99 Mb

      EASDALE central air conditioners. Installation and maintenance manual. Language: RU | pdf 1.12 Mb

      Eastdale central air conditioners. General description. Language: RU | pdf 705.99 Kb

      Chiller with water condenser series WHZ 024.2-047.2. Instructions for installation and operation. Language: RU | pdf 441.25 Kb

      Chillers with the water condenser of the PFS 106.1-314.2 series. Instructions for installation, operation and maintenance. Language: RU | pdf 938.74 Kb

      Chillers with the water condenser of the WHR 103.2-451.4 series. Reference guide. Language: RU, EN | pdf 838.97 Kb

      Chillers with the water condenser of the WHR 103.2-451.4 series. Instructions for installation and operation. Language: RU, EN | pdf 243.30 Kb

      Chillers with the water condenser of the WHS 095.1-539.4 series. Reference guide. Language: EN | pdf 400.61 Kb

      Chillers with the water condenser of the WHS 095.1-539.4 series. Help Guide (English). Language: EN | pdf 1.11 Mb

      Chillers Ecoplus 050.1 - 146.2 with water condenser. Installation, operation and maintenance manual. Language: RU | pdf 680.07 Kb

      111.1-596.2 SE ST/SE XE. Chillers Proximus Evolution (with water condenser and screw compressors). Instructions for installation and operation. Language: RU | pdf 1.17 Mb

      PFS 106.1-314.2 Chillers with water condenser. Reference guide. Language: RU | pdf 936.54 Kb

      Proximus Evolution SE 111.1-596.2, XE 111.1-596.2 Chillers with water condenser. Manual. Language: RU | pdf 967.05 Kb

      WHR 103.2 - 451.4 Chillers with water condenser. Installation and maintenance manual. Language: RU | pdf 240.95 Kb

      WHR 103.2 - 451.4 Chillers with water condenser. Reference guide. Language: RU | pdf 417.62 Kb

      WHS 095.1 - 539.4 Chillers with water condenser. Reference guide. Language: RU | pdf 398.35 Kb

      WHS E. Water cooled chillers with screw compressors. Reference guide. Language: RU | pdf 3.17 Mb

      WHZ 024.2 - 047.2 Chillers with water-cooled condenser and scroll compressors. Installation and maintenance manual. Language: RU | pdf 201.10 Kb

      WHZ 024.2 - 047.2 Chillers with water condenser. Reference guide. Language: RU | pdf 971.80 Kb

      Chillers with water cooling of the condenser and the screw compressor of the PFS "B" 103.1-296.2 series. Instructions for installation and operation. Language: EN | pdf 1.04 Mb

      Chillers with water cooling of the condenser and the screw compressor of the WHS XE 098.1-272.2 series. Instructions for installation and operation. Language: EN | pdf 980.62 Kb

      Chillers with water cooling of the condenser of the ECOPLUS 050.1-146.4 series. Instructions for installation and operation. Language: EN | pdf 1.05 Mb

      Chillers with air-cooled condenser and reciprocating compressors of the AGR 046.2 - 089.2 series. Instructions for installation and operation. Language: RU | pdf 557.50 Kb

      Chillers with air condenser and screw compressors of the ALS "D" series 163.2-460.4. Reference guide. Language: RU | pdf 1.14 Mb

MCK-A. Ceiling cassette conditioners of separate type of series A (ceiling). Installation guide. Language: RU | pdf 375.75 Kb

MCK-S. Ceiling cassette conditioners of separate type of series C (ceiling). Installation guide. Language: RU | pdf 501.84 Kb

MCK 020/025/030/040/050AR. Split air conditioners cassette type. Installation, operation and maintenance manual. Language: RU | pdf 824.71 Kb

MSK 020-050A, AR. Cassette type air conditioners. Spare parts list. Language: RU | pdf 512.03 Kb

MCM 020/025/030/040/050DR. Split air conditioners of universal (floor-ceiling) type. Manual for installation, operation and maintenance. Language: RU | pdf 934.66 Kb

MCM 020-025D. Floor-to-ceiling type air conditioners. Spare parts list. Language: RU | pdf 1.02 Mb

MWM 015/020/025 F, C, CR, FR. Split-air conditioners of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.96 Mb

MWM 007/010 E/ER. Split-air conditioners of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.50 Mb

Split air conditioners wall series G. List of changes and additions to the reference manual. Language: RU | pdf 920.69 Kb

MWM 007-025 G/GR. Split-air conditioners of wall type. Technical guide. Language: RU | pdf 3.75 Mb

MWSD 010/015/020 ER/FR/CR, MMSD, MMST. Multi-split systems of wall type. Installation, operation and maintenance manual. Language: RU | pdf 1.33 Mb

M5MSY 20/25/30BR. Multi-split systems. Technical guide. Language: RU | pdf 3.41 Mb

M5MSX 020/025/030AR. Wall-mounted multi-split systems with DC inverter. Technical guide. Language: RU | pdf 3.75 Mb

MFU. Features of installation of fan-coils of the MFU series. Installation instructions. Language: RU, EN | pdf 316.46 Kb

CK 20/25/30/40/50 AWH/ Series A fan coils for 4-pipe systems. Installation instructions. Language: RU, EN | pdf 523.89 Kb

Fan-coils of the CB and D series (ceiling-mounted). Installation instructions. Language: RU, EN | pdf 3.07 Mb

MCW 200 CD - MCW 1200 CD. Ceiling fan coils. Instructions for installation, operation and installation. Language: RU, EN | pdf 1.14 Mb

SB 75/100/125/150 BW, MDB 075/100/125/150 BW. Fan-coils of the SB series. Installation guide. Language: RU, EN | pdf 1.20 Mb

WM 05/07/10/15/20/25 FW, MWM 005/007/010/015/020/025 FW. Fan-coils with water cooling for wall installation. Installation guide. Language: RU, EN | pdf 816.15 Kb

Fan-coils of the G series (wall-mounted). Installation instructions. Language: RU, EN | pdf 2.91 Mb

MCW 200 C/H/F - MCW 1200 CHW. Frameless subceiling fan coils. Instructions for installation and operation. Language: RU, EN | pdf 720.78 Kb

Fan-coils MWM 010-025 FW. Specification. Language: RU, EN | pdf 47.65 Kb

CC 10/15/20/25 CW, CC 30/40/50/60 CW. Split-ceiling two-chamber air conditioners, with water-cooled fan. Installation guide. Language: RU, EN | pdf 596.12 Kb

MLC 07 series outdoor units B. Spare parts list. Language: RU | pdf 696.58 Kb

External blocks of the MMC 030-060 AB series. Spare parts list. Language: RU | pdf 1.52 Mb

MMSD 1010/1015/1515 series outdoor units A. Spare parts list. Language: RU | pdf 642.25 Kb

Indoor units MHSB 030-060 A/ AR. Spare parts list. Language: RU | pdf 255.50 Kb