Home Diseases and pests Refrigeration machine with a remote condenser. What are air cooled chillers. Chillers with centrifugal fans

Refrigeration machine with a remote condenser. What are air cooled chillers. Chillers with centrifugal fans

Chillers can be divided into two types according to the principle of operation and obtaining cold: vapor compression and absorption. The area of ​​application for both types of refrigeration machines is similar. Both types are mainly used for the production of coolant (refrigerant) for the needs of air conditioning, industrial refrigeration, ventilation or technology. In addition, chillers can also be used to heat a heating medium for heating and ventilation needs. Moreover, steam-compression-type units are used for heating much less frequently than absorption units due to their low efficiency at negative ambient temperatures. This article will discuss vapor compression type chillers.

Principle of operation.

The main elements of a vapor compression chiller are a compressor, an evaporator, a condenser, and a throttling device. The removal of heat energy in a vapor compression refrigeration machine occurs due to a change in the state of aggregation of a substance (refrigerant). As a rule, refrigerants are freons - fluorine and chlorine-containing derivatives of saturated hydrocarbons (mainly methane and ethane). The chiller works according to the following principle: the compressor pumps gaseous refrigerant into the condenser (see diagram in Fig. 1), where, as a result of high pressure and heat removal, the gaseous freon condenses. Further, when the liquid refrigerant passes through the throttling device, its pressure drops, while part of the liquid is converted into vapor. This process is accompanied by a decrease in its temperature. Then the vapor-liquid mixture enters the evaporator, where it boils and finally turns into steam. The evaporator is an intermediate refrigerant / water heat exchanger, in which heat is transferred from the refrigerant of the liquid to be cooled. Then the liquid of the required temperature is supplied through the hydraulic circuit to consumers - fan coil units, ventilation units, etc.

Rice. 1

Chiller classification.

Vapor compression chillers can be classified:

  1. by the type of condenser cooling;
  • air cooled condenser;
  • water cooled condenser;
  • by execution:
    • for installation outside buildings;
    • for installation inside buildings;
  • for other design features, for example:
    • with free cooling system (freecooling);
    • with a centrifugal fan for cooling the condenser;
    • by the type of compressor, etc.

    By the way of condenser cooling:

    • air-cooled chillers;
    • water-cooled chillers (water-cooled).

    Outdoor chillers are air-cooled monoblock chillers, which are usually installed on rooftops or in special areas next to buildings being serviced. Chillers with an external evaporator can also be referred to outdoor chillers.

    Indoor chillers include:

    • chillers with a remote condenser (condenserless);
    • water-cooled chillers (water-to-water chillers);
    • air cooled chillers with centrifugal fan.

    Indoor chillers are located in special rooms - machine rooms. Due to ease of installation, ease of use and price, monoblock air-cooled chillers are the most widely used.

    Monoblock air cooled chillers

    Monoblock chillers are widely used in central air conditioning systems with air handling units and in chiller-fan coil systems. Monoblocks have two modifications:

    • with axial fans;
    • with centrifugal fans (for installation inside buildings).

    Chillers with axial fans(Fig. 2) are units mounted on a frame in a single casing and installed on the roof of buildings or nearby on a prepared site. Heat is discharged into the environment.

    Rice. 2


    Water or water solutions of glycol are used as a heat carrier for the operation of the refrigerating machine in the cold season. If the requirements of the project do not allow the use of glycols, then an intermediate heat exchanger is built into the system (Fig. 3). With such a scheme, the temperature parameters of the glycol solution in the chiller should be 2 ° C lower than the design temperature in the consumer circuit. For example, in order to ensure the temperature parameters of the water in the intermediate heat exchanger outlet / inlet: 7 / 12ºC, it is necessary to obtain a glycol solution at the outlet of the chiller with a temperature of 5ºC.

    Rice. 3


    In addition, when using an intermediate heat exchanger, it is possible to operate the refrigeration machine at negative ambient temperatures. The main advantages of air-cooled monoblock chillers are ease of installation, ease of maintenance, complete readiness of the units for operation (filled with refrigerant and oil), relatively low price. Additional advantages of monoblocks include ample opportunities for placement due to the unlimited length of the coolant routes and the height difference between the chiller and consumers. Chillers of modular design also have undeniable advantages:

    • minimum delivery time due to stock availability;
    • cost savings - the system is put into operation in parts as needed;
    • variability - by combining modules of different capacities, we obtain a refrigerating machine of the required power (diagram Fig. 4);
    • energy saving - the system operates at the power level that consumers need at the moment by enabling / disabling individual modules.

    Rice. 4


    Chillers with centrifugal fans(fig. 5) are intended for installation in premises: basements, attics, service special premises. The main difference from chillers with axial fans is the high head centrifugal fan / s. The fan blows air through the duct network, which cools the condenser and then is removed to the outside, and the heat is discharged into the environment.

    Advantages of chillers with centrifugal fans:

    • long service life due to location in a heated room.

    Rice. 5


    Air intake is carried out from the room, blowing out can be organized through air ducts in one of three directions (Fig. 6)


    Hydro module. The circulation of the coolant (water, glycol solution) between the chiller and consumers (fan coil units) is provided by a hydraulic module (pumping station) (Fig. 7, a), The hydraulic module includes a circulation pump, an expansion tank, shut-off valves, a storage tank (buffer tank), control and protection system.


    A storage tank (Fig. 4, b) is required to increase the capacity of the coolant in the system. The buffer tank reduces the number of starts of compressors and pumping equipment, thereby increasing the life of the chillers. The buffer tank may not be included in the hydronic module and may be supplied separately.

    Chillers with remote condenser (condenserless) (fig. 8)

    A chiller with a remote condenser is a unit in which all the main elements: a compressor, an evaporator, a throttling device are mounted on one frame in a single casing. In this case, the chiller itself is designed for indoor installation, and the air-cooled condenser is intended for outdoor use and is installed outside.

    Rice. eight


    The main advantages of chillers with a remote condenser:

    • the possibility of year-round operation using water;
    • convenience of service at any time of the year;
    • high efficiency due to the absence of a glycol circuit and intermediate heat exchangers;
    • long service life due to location in a heated room;
    • the possibility of using a capacitor in a low-noise or explosion-proof design.

    Large spaces such as entertainment or shopping centers, hospitals, hotels, production halls and warehouses require a special air conditioning system. It should be closely related to the operation of heating and ventilation systems, and at the same time it is desirable that it not only cool the air, but also humidify or dry it, depending on the characteristics of the building. And the best of all with such tasks today are air conditioning systems built on the basis of chillers.

    What does such a system give?

    Chiller- or a special refrigeration station - considered one of the most efficient types of HVAC equipment, which allows you to create optimal temperature and humidity conditions in any room. Its main function is to cool water, after which pumping units transport cold water through pipelines to the inside of the building. At the same time, chillers can be very diverse, however, a system based on them always has a lot of advantages:

    • she gives maximum cooling efficiency(or heating if required),
    • it is economical- chillers do not consume too much electricity in comparison with other types of climatic technology,
    • she not too expensive o - the user will spend most of all only when he develops an air conditioning system - this is the most energy-intensive part of the entire project, but it will quickly pay off,
    • she multivariate- depending on the needs of the building and its inhabitants, you can choose a variety of types of equipment, equipped with a whole range of special elements.

    What are chillers?

    There are different versions of these units on sale, but only 6 varieties are considered the main ones.

    1. Chiller equipped with an air-cooled condenser function.

    As a rule, such equipment operates on water, which acts as a refrigerant. This option is considered very economical and at the same time easy from the point of view of design and subsequent installation, however, air-cooled chillers also have several disadvantages. Among them:

    • the ability to work only at positive temperatures,
    • lack of adjustment of a high level of sound pressure (its readings often go off scale for 62 dBA),
    • the possibility of complete defrosting of the chiller if the water was not drained completely or at the wrong time.

    2. Chiller equipped with an air-cooled condenser in an outdoor installation and working with anti-freeze liquids.

    As a rule, glycol acts as a heat exchanger and refrigerant in this situation, but it can also be water. Such a refrigeration station operates on a 5/10 degree schedule, and the chilled water after the heat exchanger is 7/12 degrees.

    The advantages of this system are as follows:

    • the user does not need to empty the hydraulic system every season and then refill it,
    • the chiller evaporator never defrosts,
    • the system is able to work even at negative temperatures outside,
    • in winter, such a system can be integrated with a dry cooler for free air cooling.

    On the other hand, such chillers also have disadvantages. Among them:

    • rather high price (compared to the previous model, they cost about 30% more),
    • higher energy consumption (due to glycol),
    • lower coolant temperature,
    • the presence of a second hydraulic circuit,
    • the need to use additional automation to prevent defrosting of the heat exchanger when the system is first started in winter after a long downtime.

    3. Chiller equipped with a built-in cooling tower.

    This equipment allows free cooling in cold seasons, and the automation independently selects the optimal operating mode - cooling tower only operation, compressor operation only, or mixed mode. This allows you to achieve maximum energy savings, which makes such a system very economical and allows the user to quickly recoup the costs of it.

    Another advantage of this option is that a refrigeration station with this equipment can be used without intermediate heat exchangers.

    4. Chiller equipped with a remote condenser.

    The system can effectively serve in certain conditions, however, in most cases of operation, it will be characterized only by disadvantages:

    • such a chiller is 30-40% more expensive than the first type,
    • the system cannot work all year round in regions with cold climates,
    • free cooling can be achieved only if the system will work exclusively for this function,
    • there must be a small distance between the chiller and the condenser, not exceeding 30 m,
    • the system contains too much freon,
    • to install such a chiller, only professionals with the highest qualifications are required.

    5. Chiller equipped with a liquid-cooled condenser as well as a dry cooler.

    The equipment is considered expensive, but it has many advantages:

    • such a chiller has high energy efficiency,
    • there is no threat of station defrosting at all,
    • the system can work all year round, withstanding temperatures up to -40 degrees,
    • the chiller operates almost silently,
    • the system is reliably protected,
    • the equipment can be installed on the roof, and the load on the roof will be minimal,
    • an additional free cooling function can be installed at minimal cost,
    • the distance between the chiller and the cooling tower can be unlimited,
    • the chiller does not need complicated seasonal maintenance.

    However, this technique will be about 60% more expensive than the first option.

    6. Centrifugal chiller or water-cooled station with a centrifugal compressor.

    The equipment is considered to be very efficient, and the lower the coolant temperature, the higher the efficiency of the chiller. In order to increase it additionally, an evaporative cooling tower can be used, which will maintain the water temperature at 30 degrees. This option is perfect for large buildings that require high-power systems.

    At the same time, one more important advantage of such a system should be noted - the capital costs for it are low. But, on the other hand, there are drawbacks - the cooling water circuit in such a chiller must be constantly replenished, and the minimum equipment performance will actually be 30% of the nominal value.

    7. Absorption gas chiller equipped with water cooling function.

    Liquefied gas, either imported or obtained from a gas pipeline, can be used as fuel in this equipment (to install such a chiller, a reliable connection must be made to the gas pipeline). Also, this type of refrigeration system should be completed with an evaporative cooling tower.

    If the equipment is connected correctly, it will demonstrate superior benefits:

    • minimum relative costs of consumed energy,
    • high payback,
    • the ability to generate heat in winter for space heating and hot water supply.

    At the same time, capital costs for this type of equipment will be quite high, and the minimum chiller capacity will be about 25% of the nominal value. Also, such equipment needs to recharge the cooling water circuits.

    What to choose?

    Considering all these options, it is enough to simply weigh the pros and cons, and you can roughly imagine which version of the chiller would suit you. However, the final choice should be made taking into account the specifics of the entire object and your personal wishes and requirements. In particular, you will need to consider:


    • the cost and main costs of electricity,
    • the price of connecting additional electrical capacities,
    • network natural gas price,
    • features of the climate in which you live,
    • the desired payback periods for the equipment,
    • the possibility of using an evaporative cooling tower,
    • the ability to install a refrigeration station and its elements both inside the building and outside,
    • features of the plant's operational characteristics at partial loads throughout the year,
    • parameters of the chilled liquid and your requirements for them,
    • the cost of maintenance of the chiller during the year (the price of materials and work of specialists during the year),
    • service life of the equipment.

    For example, if you need to cool the server room, be sure to keep in mind that the equipment cooling capacity must be at least 1,000 kW, the cost of connecting additional energy will be 1.5 tf. USD / kW, and the minimum outside temperature will be up to - 40. In this case, the equipment will work all year round and round the clock, and gas will not be used.

    Considering these data, the best option for a chiller for a server room would be a free-cooling system (chiller no. 5) or a chiller with a built-in cooling tower (no. 3). The latter will be 20% cheaper when purchased, and the former will turn out to be more economical later. However, in any situation, all investments in such a system (with the same cost of maintenance and the same depreciation) will be 5-7 years, after which they will give excellent savings. But if at the same time you need to connect additional electrical power (at the level of about 100 kW), the first option will definitely be more preferable from the economic point of view.

    Chillers should be selected in the same way for any other premises. And only after carrying out all the exact calculations and comparing the terms of reference with different types of stations that you could choose, you can choose the optimal climate technology.

    > Manufacturing of refrigeration equipment> Liquid cooling units> Versions and configurations of Vactekh chillers>

    Chillers with remote condenser

    Equipment "With remote condenser" it is used when it is impossible to locate equipment with significant heat generation inside the workshop or machine room (for a rough estimate, heat generation in the condenser (in kW) is 30% higher than the cooling capacity of the chiller (in kW)). The chiller itself is installed in the heated room, and the air-cooled condenser is mounted on the roof, next to the building or on the wall of the building. For some eastern regions of Russia, where the temperature in winter for a long period of time is kept at the level of -30 ... -35C, this is the only option for completing water cooling units with a cooling capacity of more than 50-100 kW. When ordering a chiller with a remote condenser, the customer is supplied with two modules: a cooling unit (the chiller itself) and an air-cooled condenser. Depending on the performance, the units are equipped with external condensers of our own production, manufactured by the company Searle(England) or HTS(Czech).

    If a chiller with a remote condenser is operated in the winter period (at an ambient temperature below 0 C), then it is equipped with a winter start-up system, which is a system of bypass valves in the freon circuit, which allows the chiller to turn on after a long stay at a low ambient temperature. All valves of the winter start-up system are built into the inside of the refrigeration unit during its manufacture.

    (chiller) is a refrigeration unit (refrigerator) for or other liquid. The chiller is designed to extract heat from the medium to be cooled at low temperatures, while the release of heat at high temperatures is a side process. The refrigeration machine contains several functional elements: a compressor (from 1 to 4), a condenser, an electric motor, an evaporator, a refrigerant expansion device or a thermostatic valve, and a control unit.

    Obtaining artificial cold is based on simple physical processes: condensation, compression and expansion of working substances. The working substances used in refrigeration units are called refrigerants.

    Chillers differ:

    • by design (absorption, with built-in or remote condenser - condenser and non-condenser);
    • type of condenser cooling (air or water);
    • connection diagrams;
    • the presence of a heat pump.

    Advantages

    • Ease of use - all year round, the set parameters are automatically maintained in each room in accordance with sanitary and hygienic standards;
    • System flexibility - the distance between the chiller and fan coil units is limited only by the pump power and can reach hundreds of meters;
    • Economic advantage - operating costs are reduced;
    • Environmental advantage - harmless refrigerant;
    • The construction advantage is the flexibility of the layout, the minimum cost of the usable area for the placement of the refrigeration machine, because it can be installed on the roof, technical floor of buildings, in the courtyard;
    • The acoustic advantage is the low-noise performance of the units;
    • Safety - the risk of flooding is limited by the use of shut-off valves.
    VMT-Ksiron chillers can only serve as a source of cold supply, but also in the reversal mode of the refrigeration or water cycle, work as a heat pump, which is in demand in the cold season.

    Chiller types

    The absorption type is a very promising area in the development of refrigeration technology, which is increasingly being used due to the pronounced modern trend towards energy saving. The fact is that for absorption refrigeration machines, the main source of energy is not electric current, but waste heat, which inevitably arises in factories, enterprises, etc. and irretrievably emitted into the atmosphere, be it hot air, air-cooled hot water, etc.

    The working substance is a solution of two, sometimes three components. The most common binary solutions of an absorber (absorbent) and a refrigerant that meet two main requirements for them: a high solubility of the refrigerant in the absorbent and a significantly higher boiling point of the absorbent compared to the refrigerant. Water-ammonia solutions (ammonia-water refrigerating machines) and lithium bromide-water (lithium bromide machines) are widely used, in which, respectively, water and lithium bromide are absorbents, and ammonia and water are refrigerants. The working cycle in absorption chillers (see the figure below) is as follows: in the generator, to which the waste heat is supplied, the working substance boils, as a result of which an almost pure refrigerant boils away, because its boiling point is much lower than that of the absorbent.

    Refrigerant vapor enters the condenser, where it cools and condenses, giving off its heat to the environment. Further, the resulting liquid is throttled, as a result of which it is cooled during expansion) and is sent to the evaporator, where, evaporating, it gives its cold to the consumer and goes to the absorber. An absorbent is supplied here through the throttle, from which the refrigerant boiled away at the very beginning, and absorbs vapors, because we have indicated above the requirement for their good solubility. Finally, the absorbent saturated with refrigerant is pumped to the generator, where it boils off again.

    The main advantages of absorption chillers:

    1. Ideal solution for creating trigeneration in the enterprise. A trigeneration complex is a complex that allows today, to minimize the cost of electricity, hot water supply, heating and cooling for an enterprise through the use of its own cogeneration power plant in conjunction with an absorption chiller;
    2. Long service life - within 20 years, before the first major overhaul;
    3. low cost of the produced cold, cold is produced almost free of charge, because absorption chillers simply recycle excess heat;
    4. Reduced noise and vibration level, as a result of the absence of compressors with electric motors, as a result - quiet operation and high reliability;
    5. The use of refrigeration / heating units with a direct fired gas generator eliminates the need for boilers, which must be used in conventional installations. This reduces the initial cost of the system and makes absorption chillers competitive with conventional systems that use boilers and chillers;
    6. Provide maximum energy savings during peak periods. In other words, without consuming electricity for the production of cold / heat, absorption chillers do not overload the power grid of the enterprise even at times of peak loads;
    7. There is the possibility of combining into steam district systems with an efficient double-effect refrigeration unit;
    8. It is possible to distribute the load under conditions of maximum performance in cooling mode. The device handles the critical load in cooling mode with minimal energy consumption through the use of chillers with a direct-operated flame gas generator or a steam-heated generator;
    9. Allows the use of emergency power generators of lower power, since the energy consumption of absorption refrigeration units is minimal when compared to electric refrigeration units;
    10. Ozone safe, does not contain ozone depleting refrigerants. Cooling is carried out without the use of substances containing chlorine;
    11. The overall impact on the environment is reduced to a minimum, since the consumption of electricity and gas, which causes the greenhouse effect and, as a result, global warming, is reduced.

    An absorption chiller is a machine that produces chilled water using residual heat from sources such as steam, hot water or hot gas. Chilled water is produced according to the principle of cooling: a liquid (refrigerant) that evaporates at a low temperature absorbs heat from its environment during evaporation. Pure water is usually used as a refrigerant, while lithium bromide (LiBr) solution is used as an absorbent.

    How absorption refrigeration systems work

    In absorption refrigeration systems, the absorbent, generator, pump and heat exchanger replace the compressor of the steam compressor cooling systems (mechanical refrigeration). The other three (3) components also found in mechanical refrigeration systems, i.e. expansion valve, evaporator and condenser, are also used in absorption refrigeration systems.

    Evaporation stage of absorption coolers

    Refer to Figure-2 for a schematic explanation of the absorption refrigeration process. Like mechanical refrigeration, the cycle "begins" when the high pressure liquid refrigerant from the condenser passes through the expansion valve (1 in FIG. 2) into the low pressure evaporator (2 in FIG. 2) and collects the Sump in the evaporator.

    At this low pressure, a small amount of Freon starts to evaporate. This evaporation process cools the remaining liquid refrigerant. Likewise, the transfer of heat from the relatively warm process water to the currently cooled refrigerant causes the latter to vaporize (2 in FIG. 2) and the resulting vapor is fed into the lower pressure absorber (3 in FIG. 2). As the process water loses heat to the refrigerant, it can be cooled to significantly lower temperatures. At this stage, chilled water is actually obtained by evaporating the freon.

    Absorption stage of absorption coolers

    The absorption of refrigerant vapors in lithium bromide is an exothermic process. In the absorber, the refrigerant is “sucked in” by the absorbing solution of lithium bromide (LiBr). This process not only creates a low pressure region that pulls a continuous flow of refrigerant vapor from the evaporator to the absorber, but also causes the vapor to condense (3 in FIG. 2) as it releases the heat of vaporization provided to the evaporator. This heat, together with the heat of dilution that occurs when the refrigerant condensate is mixed with the absorbent, is transferred to the cooling water and released in the cooling tower. Cooling water is a utility at this stage of cooling.

    Regeneration of lithium bromide solution

    As the lithium bromide absorbent absorbs the refrigerant, it becomes more and more diluted, reducing its ability to absorb more refrigerant. The absorbent must be re-concentrated to continue the cycle. This is achieved by continuously pumping the diluted solution from the absorber to a low-temperature generator (5 in Figure 2), where the addition of residual heat (hot water, steam or natural gas) boils (4, Figure 2) Refrigerant from the absorbent. This generator is often used to recover waste heat from the plant. As soon as the refrigerant is removed, the reconcentrated lithium bromide solution returns to the absorber, ready to resume the absorption process, and the free freon is sent to the condenser (6, in Fig. 2). Waste heat from steam or hot water is beneficial at this stage of regeneration.

    Condensation

    The refrigerant vapor welded in the generator (5, in Figure 2) returns to the condenser (6), where it returns to its liquid state when the cooling water raises the heat of vaporization. It then returns to the expansion valve where a full cycle is completed. During the condensation stage, the cooling water becomes useful again.

    Various technologies for absorption chillers

    Absorption chillers can be disposable, double or newer, which is a triple effect. Single effect machines have one generator (see diagram above, Figure 2) and have a COP less than 1.0. Double effect machines have two generators and two capacitors and are more efficient (typical COP values> 1.0). Triple effect machines add a third generator and capacitor and are most efficient: COP> 1.5 typical.

    Pros and cons of absorption chiller systems

    The main advantage of absorption chillers is lower energy costs. Costs can be further reduced if natural gas is available at a low cost or if we can use a low-grade heat source that would otherwise be lost in the plant.

    The two main disadvantages of absorption systems are their size-weight, and their need for larger cooling towers. Absorbent chillers are larger and heavier in comparison with electric chillers of the same capacity.

    Vapor compression chillers are currently the most common type of refrigeration equipment. Cold generation is carried out in a vapor compression cycle, which consists of four main processes - compression, condensation, throttling and evaporation - using four main elements - a compressor, a condenser, a control valve and an evaporator - in the following sequence: Working substance (refrigerant) in a gaseous state enters compressor inlet with pressure P1 (~ 7 atm) and temperature T1 (~ 5 ° C) and compressed there to pressure P2 (~ 30 atm), heating up to temperature T2 (~ 80 ° C).

    Then the freon goes to the condenser, where it is cooled (as a rule, due to the environment) to the temperature T3 (~ 45C), while the pressure ideally remains unchanged, but in reality it drops by tenths of an atm. During the cooling process, freon condenses and the resulting liquid enters the throttle (element with high hydrodynamic resistance), where it expands very quickly. At the outlet, a vapor-liquid mixture with parameters P4 (~ 7 atm) and T4 (~ 0С) is obtained, which enters the evaporator. Here, freon gives up its cold to the coolant flowing around the evaporator, heating up and evaporating at constant pressure (in reality, it will fall by tenths of an atmosphere). The resulting cooled heat carrier (Tx ~ 7C) is the final product. And it has parameters P1 and T1 at the outlet of the evaporator, with which it enters the compressor. The cycle is closed. The driving force is the compressor.

    Refrigerant and heat carrier

    We especially note the separation of similar at first glance terms - refrigerant and coolant. Refrigerant is a working substance of the refrigeration cycle, during which it can be in a wide range of pressures and also undergo phase changes. The coolant does not change (phase changes) and serves to transfer (transfer) heat (cold) over a certain distance. Of course, an analogy can be drawn by saying that the driving force of the refrigerant is a compressor with a compression ratio of about 3, and the coolant is a pump that increases the pressure by 1.5-2.5 times, i.e. the figures are comparable, but the fact of the presence of phase changes in the refrigerant is fundamental. In other words, the coolant always works at temperatures below the boiling point for the current pressure, while the coolant can have a temperature both below and above the boiling point.

    Classification of vapor compression chillers

    By installation type:

    Outdoor installation (built-in condenser)

    Such units represent a single monoblock installed outdoors. Convenient in that it allows you to exploit unexploited areas - the roof, open areas on the ground, etc. It is also a cheaper solution. At the same time, the use of water as a coolant is associated with the need to drain it for the winter period, which is inconvenient in operation, therefore non-freezing liquids are used, both new salt and traditional - solutions of glycols in water. In this case, it is necessary to recalculate the operation of the chiller for each specific coolant. Note that all today's antifreeze solutions are 15-20% less effective than water. The latter is generally difficult to surpass - the heat capacity and density, high by the standards of liquids, make it an almost ideal heat carrier, if it were not for such a high freezing point.

    Indoor installation (remote condenser)

    Here the situation is practically the opposite compared to the previous version. The chiller consists of two parts - a compressor-evaporation unit and a condenser, connected by a freon line. Sometimes quite valuable areas are required inside the building, while space is still needed outside for placing the condenser, albeit with significantly lower requirements both in terms of area and weight. Indoor chillers have no problem with water use. We also mention the slightly higher energy consumption of the compressor and the increased pressure loss due to the extended route (from the chiller to the condenser), which, by the way, is also limited in length by the compressor.

    By the type of condenser version:

    This is the most common option. The condenser is a finned tube heat exchanger and is cooled with free outside air. It is both cheap and easy to design, install and operate. Perhaps the only drawback is the large dimensions of the condenser due to the low air density.

    Water cooling

    However, in some cases water-cooled condenser is used. In this case, the condenser is a plate, plate-fin or tube-in-tube heat exchanger. Water cooling significantly reduces the dimensions of the condenser and also allows for heat recovery. But the resulting heated water (about 40C) is not a valuable product; often it is simply sent for cooling to cooling towers, again giving off all the heat to the environment. Thus, water cooling is really beneficial if there is a consumer of heated water. In any case, water-cooled chillers are more expensive than air-cooled chillers, and the entire system as a whole is more complex in design, installation and operation.

    Traditionally, cooling towers are used to cool the condenser of refrigeration machines, in which water heated in the condenser is sprayed through nozzles in a stream of moving outside air, and in direct contact with the air is cooled to the temperature of a wet outside air thermometer, then entering the condenser. This is a rather bulky device that requires special maintenance, installation of a pump and other auxiliary equipment. Recently, so-called "dry" cooling towers or condenser coolers have been used, which represent a surface water-to-air heat exchanger with axial fans, in which the heat of water heated in the condenser is transferred to air, which is circulated through the heat exchanger by axial fans.

    In the first case, the water circuit is open, in the second case, it is closed, in which it is necessary to install all the necessary equipment: a circulation pump, an expansion tank, a safety valve, and shut-off valves. To prevent water freezing when the chiller is operating in cooling mode at negative outdoor temperatures, the closed circuit is filled with an aqueous solution of antifreeze liquid. When a condenser is water cooled, the heat of condensation is also wasted and contributes to thermal pollution of the environment. If there is a heat source, such as a hot water supply system or a process line, it may be useful to use the heat of condensation during the cold generation period.

    By the type of hydronic module:

    Chillers of this configuration are a monoblock, which includes a pump group and, as a rule, an expansion tank. Obviously, manufacturers produce standard hydronic modules most often of two modifications - with less and more powerful pumps, which do not always meet the necessary requirements (usually their pressure may simply not be enough). In addition, the built-in hydronic module in outdoor chillers will be located outdoors, which can create problems in winter - the non-freezing coolant can thicken and in the first seconds of operation the pumps are not able to overcome its viscosity and will not start. On the other hand, there is no need to look for a place for a pumping station, think over its layout, etc. plus there are no problems with automation - these are very significant advantages of built-in hydronic modules.

    With external hydronic module

    The remote hydronic module is used, firstly, when the built-in power is not enough; secondly, if there is a need for redundancy (note that one standby pump is allowed in the built-in hydronic modules); thirdly, if for some reason the internal installation of the pumps is desirable. The system becomes flexible, and the length of the route is practically unlimited, because the pumps are also very powerful. At the same time, there are ready-made pumping stations, which include pumps and an expansion tank and automation, and are compactly assembled on a support frame.


    By type of condenser fans:


    Chiller options

    - free cooling function. Practically indispensable for chillers operating in cold seasons. A reasonable question arises, why use a vapor compression cycle for cooling, if it is already cold outside. The answer comes by itself - the coolant should be directly cooled with street air. In the refrigeration system, the most common temperature schedule is 7 / 12C, which means that theoretically, at street temperatures below 7C, it is already possible to use free cooling. In practice, due to underrecovery, the area of ​​application is somewhat narrowed - at temperatures of 0C and below, the refrigerating capacity from freecooling reaches nominal values.

    Body pump- this is the chiller operating mode “for heating”. The vapor compression cycle works in a slightly different sequence, the evaporator and condenser change their roles and the coolant is not cooled, but heated. By the way, let us note that although the chiller is a refrigeration machine, which gives three times more cold than it consumes, it is even more efficient as a heater - it will give four times more heat than it consumes electricity. The heat pump mode is most common in public and administrative buildings, sometimes used for warehouses, etc.

    Compressor soft start- an option that allows you to get rid of high starting currents exceeding the working ones by 2-3 times.

    Chiller typology

    The source of cold in air-water air conditioning systems is a chiller - a water-cooled chiller. There are chillers of various types depending on the method of condenser cooling, the type of equipment: monoblock or with a remote condenser, with or without a built-in hydronic module, operating mode (cooling only or cooling and heating). Manufacturers are constantly modernizing their equipment based on the latest technological and design developments.

    The range of chillers produced in recent years has been significantly updated due to the widespread use of new more efficient types of compressors: scroll, single-screw, twin-screw, which in the range of small, medium and large capacities are gradually replacing reciprocating compressors. The range of chillers with an integrated hydraulic module has been expanded, including those with an accumulation tank.

    Plate and surface heat exchangers are more often used as evaporators, which made it possible to reduce the dimensions of the units and their weight. Recently, manufacturers have begun to issue chillers based on environmentally friendly R407 ° C freons,. Depending on the method of condenser cooling, refrigeration units are divided into air-cooled and water-cooled chillers. Chillers with an air-cooled condenser are most widely used, when the heat from the condenser is removed by air, usually outside.

    This method of heat removal requires installing it outside the building or using special measures to ensure this method of cooling. Air-cooled chillers are available in monoblock design, when all the elements of the chiller are in one unit, and chillers with a remote condenser, when the main unit can be installed indoors, and the condenser, cooled by outdoor air, is located outside the building, for example, on the roof or in the yard. ... The main unit is connected to an air condenser installed outside the building with copper freon lines.

    Monoblock chillers

    Chillers with axial fans

    Monoblock chillers are available with axial fans and centrifugal fans. Axial fans cannot operate on the ventilation network, therefore, chillers with axial fans should be installed only outside the building, and nothing should interfere with the flow of air into the condenser and its release by the fans. Chillers with axial fans can be manufactured in various versions: 1 - standard, 2 - with full heat recovery, 3 - with partial heat recovery, 4 - for cooling an antifreeze water solution of ethylene glycol in the operating temperature range from + 4 ° C to −7 ° WITH.

    The chiller can be executed with an additional method of cold capacity regulation. With chiller versions 1, 3, the heat of condensation is transferred to the outside air and is irretrievably lost. In versions 2 and 4 of chillers, additional shell-and-tube heat exchangers are installed, duplicating the condenser completely in the R version (using 100% of the condensation heat for heating water) or partially (using 15% of the condensing heat for heating water).

    In option 4, an additional shell-and-tube condenser is installed on the discharge line after the compressor and upstream of the main air condenser. Chiller configuration can be: ST-standard; LN - with a reduced noise level, which is achieved by the device of a sound-absorbing casing for the compressor and a decrease in the rotational speed of the axial fan of the condenser in comparison with the standard configuration; EN - with a significant reduction in the noise level, which is achieved by the device of a sound-absorbing casing for the compressor, an increase in the free area of ​​the condenser for the passage of air and a decrease in the rotation speed of the axial fan, as well as the installation of the compressor on spring anti-vibration mountings, the use of flexible inserts on the discharge and suction pipelines of the refrigeration contour.

    The sound power requirements of an operating chiller with axial fans when installed outside a building may not be very high if there are no specific requirements for noise in the building where the building is located. If such restrictions apply, the sound pressure level in the room must be calculated for the noise emitted by the chiller and, if necessary, chillers with a special configuration must be used.

    Chillers with centrifugal fans

    Chillers with centrifugal fans are designed for indoor installation. The main requirements for these units are: compactness and low noise level associated with indoor installation. In chillers of this type, centrifugal fans with low rotation speed are used, most of the small and medium-sized standard sizes have a scroll compressor, which is characterized by a low noise level; in sizes with a hermetic reciprocating compressor, it is placed in a special sound-insulating casing. The side panels of the casing of such chillers have a sound-absorbing coating from the inside; along with the standard ST configuration, the SC configuration with a low noise level is provided, where a semi-hermetic reciprocating compressor is placed in a sound-absorbing casing and there are flexible inserts on the discharge and suction pipelines of the refrigeration circuit.

    When choosing this type of chiller and placing it, ensure free supply of cooling air to the chiller and removal of air heated in the condenser. This is done with the help of suction and discharge air ducts, while a ventilation network is formed, consisting of a centrifugal fan, an air heater (chiller condenser), air ducts, intake and outlet ventilation louvers. The dimensions of the latter are selected on the basis of the recommended speeds of air movement in the cross-section of the grilles and air ducts.

    It is necessary to determine the pressure loss in the ventilation network on the basis of an aerodynamic calculation. The pressure loss in the ventilation network must correspond to the pressure developed by the centrifugal fan at the value of the air flow rate that cools the condenser. If the pressure of the centrifugal fan is less than the pressure loss in the ventilation network, a more powerful electric motor can be applied to the centrifugal fan by special order. The air ducts must be connected to the chiller with flexible connectors so that vibration is not transmitted to the ventilation network.

    Chiller performance

    Depending on the capacity, the chillers are equipped with three types of compressors: scroll compressors for small (recently shifted towards medium) capacity, single-screw compressors for medium and large capacity, twin-screw compressors for medium capacity, hermetic reciprocating compressors for small capacity and semi-hermetic reciprocating compressors for average productivity. Scroll and screw compressors, being more efficient in a certain range of capacities in comparison with reciprocating ones, are gradually replacing the latter. Chillers are produced in two versions: operating only in the refrigeration machine mode and operating in two modes: refrigeration machine and heat. Chillers with air-cooled condenser, which are provided for operation in the heat pump mode, provide for reversal of the refrigeration cycle, in water-cooled chillers, reversal along the water circuit is provided.

    Chiller diagram with integrated hydraulic module

    In the version, the chiller block includes: a circulation pump on the return line, a membrane expansion tank, a safety valve for water, a drain valve, a water filling unit, a pressure gauge, and a differential pressure switch.

    Energy saving technologies in chillers

    When developing modern climatic equipment, special attention is paid to the problem of energy saving. In Europe, the amount of energy consumed by equipment during an annual operating cycle is one of the main decision criteria when considering proposals submitted for tenders. Today, a significant potential for improving energy efficiency is the development and creation of climatic technology capable of covering the load schedule as accurately as possible under constantly changing operating conditions. For example, according to research carried out by Clivet, fluctuations in the average load on the air conditioning system during the season are up to 80%, while operating at full capacity is required only a few days a year.

    At the same time, the daily schedule of heat surpluses also has an irregular character with a pronounced maximum. Traditionally, chillers with a capacity of 20–80 kW are equipped with two identical compressors and make two independent refrigeration circuits. As a result, the unit is able to operate in two modes at 50% and 100% of its rated power. The new generation of chillers with a cooling capacity of 20 to 80 kW allows three-stage capacity control. In this case, the total refrigeration capacity is shared between the compressors in a ratio of 63% and 37%.

    In new generation chillers, both compressors are connected in parallel and operate on one refrigeration circuit, that is, they have a common condenser and evaporator. This arrangement significantly increases the energy conversion factor (KPI) of the refrigeration circuit when operating at partial load. For such chillers at 100% load and an outdoor temperature of 25 ° C, KPI = 4, and when operating at 37%, KPI = 5. Considering that 50% of the time the chiller operates at 37% load, this gives significant energy savings.

    To effectively implement the new solution, microprocessor controllers are installed on the chillers, which allow:
    • control all operating parameters of the equipment;
    • regulate the set value of the temperature of the water leaving the chiller in accordance with the parameters of the outside air, technological processes or commands from the centralized control system (dispatch);
    • to select the optimal step of power regulation;
    • perform a defrost cycle quickly and efficiently when really needed (for heat pump models).

    As a result, short-term compressor start-ups are automatically minimized, the compressor operating time is optimized and the parameters of the water leaving the chillers are adjusted in accordance with real needs. As shown by the tests carried out, on average, only 22 compressor switch-ons occur during the day, while the compressors of conventional chillers are switched on 72 times.

    The average annual KPI of the chiller reaches 6, and the energy savings, when using modern chillers instead of conventional ones, is 7.5 kWh per 1 m2 of the area of ​​the serviced facility per season, or 35%. Another important advantage that the use of new chillers provides is that the need for bulky storage tanks is eliminated, and a circulation pump built into the chiller body eliminates the need for an additional pumping station.

    As you know, the type of compressors used is of great importance for the accuracy of the chiller load schedule. Traditionally, high capacity chillers have used reciprocating or screw compressors. A piston compressor has a large number of moving parts and, as a result, low efficiency due to high friction losses. During operation of reciprocating compressors, there is a high level of noise and vibration, and there is also a need for their regular maintenance. Screw compressors, in turn, have a complex design and, as a result, are very expensive. The production of screw compressors turns out to be unprofitable.

    Maintenance of such compressors is laborious and requires highly qualified personnel. In recent years, new SCROLL compressors have appeared on the market, which are devoid of the characteristic disadvantages of reciprocating and screw compressors. Scroll compressors are energy efficient, low noise and vibration, and are maintenance free. This type of compressor is simple in design, very reliable and, at the same time, inexpensive. However, Scroll compressors usually do not exceed 40 kW.

    The use of many small but very reliable Scroll compressors in modern chillers, as well as several refrigeration circuits, has made it possible to obtain a very "maneuverable" chiller that is capable of delivering the required refrigeration power with high precision. Obviously, the use of such a chiller makes it unnecessary to install a pumping station, and a wide selection of pumps of different capacities built into the chiller body solves all issues related to the circulation of chilled water. The very small inrush currents of new equipment deserve special mention. After all, the start-up of small Scroll compressors with low power consumption takes place alternately, in accordance with the increase in the load on the unit.

    All chillers of the latest generations have a modern microprocessor control system that allows you to adjust the set value of the temperature of the water leaving the chiller in accordance with the outdoor air parameters, technological processes or commands from a centralized control system (dispatch). From an economic point of view, using a large number of Scroll compressors and installing an integrated circulation pump instead of a separate pumping station turns out to be a more profitable option than using expensive, powerful and complex semi-hermetic compressors.

    Advantages and disadvantages of chillers

    Advantages

    Compared to split systems, in which gas refrigerant circulates between the chiller and local units, chiller-fan coil systems have the following advantages:
    • Scalability. The number of fan coil units (loads) on a central refrigeration machine (chiller) is practically limited only by its capacity.
    • Minimum volume and area. The air conditioning system of a large building can contain a single chiller, occupying the minimum volume and area, the appearance of the facade is preserved due to the absence of external air conditioning units.
    • Virtually unlimited distance between chiller and fan coil units. The length of the routes can reach hundreds of meters, since with a high heat capacity of the liquid heat carrier, the specific losses per linear meter of the route are much lower than in systems with a gas refrigerant.
    • Wiring cost. To connect chillers and fan coil units, ordinary water pipes, shut-off valves, etc. are used. Balancing water pipes, that is, equalizing the pressure and flow rate of water between individual fan coil units, is much easier and cheaper than in gas-filled systems.
    • Security. Potentially volatile gases (refrigerant gas) are concentrated in the chiller, which is usually installed in air (on the roof or directly on the ground). Internal piping failures are limited by the risk of flooding, which can be mitigated by automatic shut-off valves.

    disadvantages

    • Chiller-fan coil systems, in a strict sense, are not ventilation systems - they cool the air in each conditioned room, but do not affect the air circulation in any way. Therefore, to ensure air exchange, chiller-fan coil systems are combined with air (roof) air conditioning systems, the chillers of which cool the outside air and supply it to the premises via a parallel forced ventilation system.
    • Being more economical than rooftop systems, chiller-fan coil systems are certainly inferior in terms of economics to VRV and VRF systems. However, the cost of VRV systems remains significantly higher, and their marginal performance (volumes of refrigerated rooms) is limited (up to several thousand cubic meters).
    • Some aspects of refrigeration design
    • A refrigeration machine is an oversized (all three dimensions significantly exceed a meter, and the length can exceed 10m) and heavy (up to 15 tons) equipment. In practice, this means an almost unconditional need for the use of unloading frames to distribute the mass of the chiller over a large area with the choice of acceptable support points. Standard frames are not always suitable for each specific case, therefore, more often than not, special design is required.
    • The chiller VMT-Ksiron has 1-4 compressors, 1-12 fans, 1-2 pumps, which causes a whole range of negative vibrations, therefore, the chiller is certainly installed on vibration dampers of the appropriate bearing capacity, and all pipelines are connected through expansion joints of the corresponding diameter ...
    • As a rule, the connecting diameters of the chiller pipelines are smaller than the main pipe (more often one, sometimes two standard sizes), therefore, a transition is required. It is recommended to install an expansion joint directly at the chiller and immediately follow the transition. Due to significant hydraulic losses, it is not recommended to remove the transition from the unit.
    • To avoid clogging of the evaporator on the coolant side, a filter must be installed at the chiller inlet.
    • In the case of a built-in hydronic module, there must be a check valve at the outlet of the chiller to avoid water movement against the design.
    • To regulate the forward and reverse flows, a jumper between them with a differential pressure regulator is recommended.
    • Finally, in the documentation, you should always pay attention to which heat carrier the data is given for. The use of an anti-freeze coolant reduces the efficiency of the refrigeration system by an average of 15-20%.

    Hydraulic diagram of the chiller, hydronic module

    Chiller operation diagram with air condenser and winter start system (monoblock version, without hydronic module)


    Specification

    1. Danfoss compressor
    2. High pressure switch KR
    3. Shut-off valve Rotolock
    4. Differential valve NRD
    5. Linear receiver
    6. Shut-off valve Rotolock
    7. Filter drier DML
    8. Sight glass SG
    9. Solenoid valve EVR
    10. Thermostatic valve TE
    11. DAS / DCR filter drier
    12. Low pressure switch KP
    13. Shut-off valve Rotolock
    14. Temperature sensor AKS
    15. Liquid flow switch FQS
    16. Electric shield
    Danfoss

    Chiller operation diagram with remote air condenser and winter start system (without hydronic module)


    Specification

    1. Danfoss compressor
    2. High pressure switch KR
    3. Shut-off valve Rotolock
    4. Oil separator OUB
    5. Non-return valve NRV
    6. Differential valve NRD
    7. Condensing pressure regulator KVR
    8. Ball valve GBC
    9. Air cooled condenser
    10. Ball valve GBC
    11. Non-return valve NRV
    12. Linear receiver
    13. Shut-off valve Rotolock
    14. Filter drier DML
    15. Sight glass SG
    16. Solenoid valve EVR
    17. Coil for Danfoss solenoid valve
    18. Thermostatic valve TE
    19. Evaporator plate brazed type B (Danfoss)
    20. DAS / DCR filter drier
    21. Low pressure switch KP
    22. Shut-off valve Rotolock
    23. Temperature sensor AKS
    24. Liquid flow switch FQS
    25. Electric shield
    Scheme developed and provided by Danfoss

    Operation diagram of a chiller with a water-cooled condenser and with condensing pressure control


    Specification

    1. Danfoss compressor
    2. High pressure switch KP
    3. Shut-off valve Rotolock
    4. Brazed plate water-cooled condenser type B (Danfoss)
    5. Water regulating valve WVFX
    6. Filter drier DML
    7. Sight glass SG
    8. Solenoid valve EVR
    9. Coil for Danfoss solenoid valve
    10. Thermostatic valve TE
    11. Evaporator plate brazed type B (Danfoss)
    12. DAS / DCR filter drier
    13. Low pressure switch KP
    14. Shut-off valve Rotolock
    15. Temperature sensor AKS
    16. Liquid flow switch FQS
    17. Electric shield
    Scheme developed and provided by Danfoss

    Diagram of the hydronic module for a chiller with one pump

    Specification:

    1. Open-type thermally insulated container
    2. Pump
    3. Ball valve
    4. Collapsible connection
    5. Pressure gauge
    6. Access to the consumer
    7. Water inlet
    8. Bypass valve
    9. Coarse filter
    10. Flow control relay
    11. Visual control of liquid level

    What is a fan coil unit: principle of operation and a guide for choosing a device

    A fan coil unit is an indoor unit of an air conditioning system of the chiller-fan coil type, capable of cooling or heating the air entering it. It is used to maintain the required microclimate in the room throughout the year. This article discusses the principle of operation of such devices, their varieties, as well as the main pros and cons.

    A fan coil unit, also called a fan coil unit, consists of two main elements: a heat exchanger (radiator) and a fan. Many models also have a coarse filter - it prevents dust and dirt from getting inside the case. The equipment must be located indoors and connected to the chiller (machine, cooling or heating fluid for transferring heat energy) using a piping network.

    According to the principle of operation, the fan coil unit is very similar to the internal block of the split system. The main difference lies in the coolant: instead of coolant, the fan coil uses ordinary water or an antifreeze solution. The liquid cools or heats the incoming air, which is brought to the desired temperature and returned to the room. The resulting condensate is discharged to the street or to the sewer using a pump.

    As in the case of heating radiators, several fan coil units are often installed in one room at once - the required number depends on the power of the devices and the area of ​​the room. In addition, they can be connected to supply ventilation, which allows the devices to be used in a mixed mode (to mix the air received from the inside with fresh air).

    Temperature control is carried out using the electronic system control unit, temperature sensors and various valves. Complex air conditioning systems also use central air conditioners, which are responsible for cleaning and humidifying the incoming air.

    Chiller-fan coil system types

    There are two main types of chiller-fan coil systems:
    • Single-zone system... It is mainly used for servicing large premises with a uniform heat distribution, since all single-circuit fan coil units connected to it are heated and cooled at the same time.
    • Multi-zone system... Uses fan coil units with double-circuit heat exchangers, which allows the supply of cold and hot water to be separated. Devices in such a system can simultaneously provide different air temperatures in different rooms.

    Varieties of fan coil units

    All fan coil units work according to the same principle - the devices differ only in the way they are installed. There are four main types of fan coil units:
    • Cassette;
    • Outdoor;
    • Wall-mounted;
    • Duct.
    Each of these types is discussed in detail below.

    This type of device is often used in air conditioning systems for offices or commercial premises with high false ceilings, since they can be installed in them. Cassette fan coil units are available in the following varieties:
    • Single-flow (air is discharged from the device in one direction);
    • Double-flow (two air flows out of the device in different directions);
    • Quadruple (models of this type release four air streams, making them the best choice for air conditioning large areas).

    The simplest type of fan coil in terms of installation with an external casing, which is fixed to the floor. The most efficient location for the floor unit is in front of the windows, as the outgoing air currents are directed towards the ceiling, creating an effective thermal curtain. These fan coil units can be supplied with both built-in and remote controls.

    Like floor standing units, wall mounted fan coil units are protected by decorative enclosures. They are quickly mounted on the wall in any suitable place in the room. Most often they are installed above the door. Almost all wall-mounted units are equipped with convenient remote controls.

    Unlike wall-mounted or floor-standing units, ducted fan coil units do not have a housing - they are installed directly into ventilation shafts. Devices of this type are mainly used for cooling or heating air in spacious rooms that require high-performance air conditioning systems (salesrooms, cinemas, entertainment centers, production halls, etc.).

    How to choose a fan coil unit

    When choosing a fan coil, the following device parameters should be considered:
    • Type (cassette, floor, wall or duct);
    • Power (the minimum indicator in watts can be obtained by multiplying the area of ​​the air-conditioned room by 100);
    • Energy efficiency (relevant only for large air conditioning systems, since fan coil units consume quite a bit of electricity);
    • Noise level (it is recommended to use devices with quiet fans, the noise level of which does not exceed 60 decibels).

    Advantages and disadvantages of fan coil units

    Chiller-fan coil systems are popular for a number of advantages over traditional split systems. Among the advantages are:
    • Scalability. The distance between units in split systems does not exceed 15 meters due to the refrigerant used in them. At the same time, the distance between the chiller and fan coil unit can exceed hundreds of meters, making it easy to expand the system if necessary.
    • Versatility. Unlike air conditioners in standard split systems, fan coil units are capable of operating non-stop all year round.
    • Security. Fan coil units are much safer than gas refrigerants used in split systems.
    Unfortunately, fan coil units also have disadvantages. These include:
    • Large system sizes. Due to the impressive dimensions of the chiller-fan coil system, its installation is advisable only in spacious buildings.
    • Poor filtration quality. Air purification filters built into fan coil units do their job much worse than their counterparts in split systems.
    • High complexity of installation. Due to the large size and weight of chiller-fan coil systems, installation takes a lot of time and effort.

    Drycoolers: features of work and types of devices

    Dry cooler, or - is a ventilator used to cool the coolant by blowing outside air. It is used both in small air conditioning systems - fan coil chiller, and in large industrial plants. On this page you can find basic information about dry coolers, as well as a list of the most famous manufacturers of these devices.

    How a dry cooler works

    There are three main components in the design of a dry cooler:
    • Plate heat exchanger. Can be V-shaped, horizontal or vertical. Most often made from aluminum or copper. Efficient heat transfer is ensured by the high number of fins and, as a result, the large surface area of ​​the heat exchanger.
    • One or more fans. Most drycoolers are equipped with axial cooling impellers with a radius of 200 to 350 mm. In large units with V-shaped heat exchangers, fans with a diameter of up to 1000 mm are allowed. In addition, centrifugal fans can be used in high-performance industrial cooling systems.
    • Protective and regulating automatic equipment responsible for maintaining the required temperature of the coolant and changing the speed of the fans.
    • The heated coolant (ordinary water or antifreeze solution) is supplied to the inlet of the dry cooler, where its temperature is reduced to the temperature of the outside air. The cooling level can be adjusted by changing the speed of the fans. The liquid is supplied using a circulation pump. After that, the cold heat carrier is fed back to the cooled equipment, and then the cycle is repeated.

    Advantages and Disadvantages of Dry Coolers

    Drycoolers have a number of advantages. These include:
    • High energy efficiency;
    • Environmental safety (the energy carrier circulates in a closed loop, and, as a result, does not evaporate, keeping the air humidity at the same level);
    • Easy to install, operate and service;
    • Low cost of equipment;
    • Ease of scaling (new units can be easily added to the existing cooling system);
    • When working with dry coolers, you can use any anti-freeze solutions.
    At the same time, dry coolers have several significant disadvantages:
    • The performance of devices depends on the temperature of the outside air (problems are possible during periods of peak temperatures in winter and summer);
    • Drycoolers use more energy than standard evaporative cooling towers.

    Dry coolers application area

    Due to their good energy efficiency and low cost, drycoolers are popular in a number of applications. They can work both independently and as auxiliary equipment together with refrigerators. In particular, dry cooling towers are used:
    • In industries requiring large volumes of coolant;
    • In industry for cooling heat carriers in refrigeration and injection molding equipment, as well as removing heat from motors of extruders, machine tools and generators;
    • In construction, to reduce the temperature of refrigeration plants and power generators;
    • For free cooling of air in public and industrial buildings (freecooling).
    • A wide range of models and configurations of drycoolers allows you to select a unit with suitable characteristics for any operating conditions, therefore, their popularity only increases every year.

    A chiller with a remote condenser is similar in design to chillers based on a water condenser. The chiller itself is installed indoors, and the condenser is outside. They are interconnected by a system of freon lines. These chillers are available in several versions. They can vary in power and can be equipped with automatic control systems. The compact indoor unit does not require much indoor space, and the remote condenser is reliably protected from weather conditions.

    The main difference of such a chiller from analogs with a water condenser is that in its circuit:

      It is not necessary to use an intermediate heating medium and powerful circulation pumps. The probability of the heating medium freezing is minimal, so there is no need to use a two-circuit refrigeration system.
    There are no problems with the use of water, but energy costs increase, since the gap from the chiller to the condenser is much longer and is limited in length by the condenser, so pressure losses will inevitably occur. And the loss of temperature of the refrigerant reduces its efficiency and increases energy consumption. The chiller with remote condenser consists of two different units. In one of them there is a refrigeration unit, in the second a condenser based on water cooling. This design makes it possible to:
      Place only the chiller itself indoors, while the noisiest part of the equipment is the condenser installed on the outer wall of the building or its roof, thereby reducing the noise level in the room and saving the interior space. Both units are connected with refrigerant pipes.

    5 reasons to buy chillers from AkvilonStroyMontazh

    1. Attractive prices and flexible system of discounts
    1. All necessary accompanying documents
    1. Warranty service for purchased equipment
    1. Huge selection of products
    1. High quality and the shortest possible lead times

    SUBMIT YOUR APPLICATION

    Advantages of a chiller with a remote condenser Such chillers have a number of advantages:
      Ease of maintenance of the unit. The automation system is reliably protected from adverse weather conditions. Since the entire piping system is located inside the room, there is no need to use anti-freezing liquids. Ordinary water can be used as a heat carrier. Therefore, this type of chiller is usually based on a refrigeration unit with a water condenser. Chillers of this type can be operated all year round for the air conditioning of industrial premises.
    The only drawback is the limitation of the length of the pipelines between the compressor-refrigeration unit and the condenser. Manufacturers of such equipment produce types of chillers, which, thanks to a remote condenser, have a wide range of capacities and are fully equipped with automation. This makes it possible to regulate energy consumption and successfully air-conditioning industrial and residential buildings.

    New on the site

    >

    Most popular